Toshiba LF232*F Instruction Manual
TIC-LF502A
2
Required straight pipe length:
10D minimum on upstream side and
5D minimum on downstream side
Note: D is a nominal meter size.
Fluid conductivity: 100µS/cm minimum
Fluid temperature: 32 to 131 °F (0 to 55 °C )
Ambient temperature: 14 to 122 °F (-10 to 50 °C )
Dimensions and Weights: See figures 3 to 5.
Power supply:
100 to 120 Vac (80 to 132 Vac), 50/60Hz
Power consumption: 50VA (30W) or less
■
Model LF502 Detector
Meter sizes: 6” (150 mm ), 8” (200 mm ), 10” (250
mm ), 12” (300 mm ), 14” (350 mm ), 16” (400
mm ), 20” (500 mm ), 24”(600 mm )
Fluid pressure:
0 psi or 0 bar (0 MPa) to the pressure limited by
flange standard
(fully-filled condition)
(fully-filled condition)
Connection flange standards:
ANSI 150, JIS 10K
Structure:
IP67 and NEMA 4X Watertight (std. )
IP68 and NEMA 6P Submersible (opt.)
Coating: Phthalic acid resin coating, pearl-gray
colored (standard for watertight type) or black tar
epoxy (option for watertight type and specified
exclusively for submersible type)
Principal materials:
Case — carbon steel
Measuring pipe — 304 stainless steel
Linings — The following are the standards:
Measuring pipe — 304 stainless steel
Linings — The following are the standards:
Meter size
Standard specification
6” to 16” (150 to 400mm )
EPDM rubber
20” & 24” (500 & 600mm )
Chloroprene rubber
Electrodes — 316L stainless steel (std.)
Grounding rings — The following are the
Grounding rings — The following are the
standards.
Meter size
Standard specification
6” to 16” (150 to 400mm )
316 stainless steel
20” & 24” (500 & 600mm )
304 stainless steel
See Table 1 for optional materials and other
related information.
Coating: phthalic acid resin coating (std.),
Pearl-gray colored
Pearl-gray colored
Cable connection port:
Cable glands: Provided as standard, R(PT) 1/2
male screw.
Applicable diameter: 0.433 to 0.512 inch (11
to 13mm )
■
Model LF232*F converter
Input signals
Analog signal — the voltage signal from detector,
proportional to process flow rate.
Digital input DI (opt.)
(added when 9
(added when 9
th
digit of specification code is ”3”)
Voltage level: High level 20 to 30 V dc
Low level 2 V dc or less
Input resistance: 2.7 k
Ω
Number of inputs: 2 points (DI1 and DI2)
DI functions:
For digital input function, either of the following
functions can be selected.
functions can be selected.
• Range switching
One Digital Input is used: switching between large
and small ranges of forward/reverse, 2-range
measurement.
Two Digital Inputs are used: switching between
ranges of single direction, 4-range measurement.
and small ranges of forward/reverse, 2-range
measurement.
Two Digital Inputs are used: switching between
ranges of single direction, 4-range measurement.
• Totalizer control input
Totalizer Start/Stop control or Reset/Start
•Output hold input
Totalizer Start/Stop control or Reset/Start
•Output hold input
Fixed with set value for current output and pulse
output (loop check)
output (loop check)
• Zero adjustment
Starts zero adjustment (on-stream at zero flow rate)
when DI voltage level goes low after remaining
high for 10 to 20 seconds.
when DI voltage level goes low after remaining
high for 10 to 20 seconds.
Output signals
Current output:
4–20mAdc (load resistance 0 to 1K
Ω)
Digital output (DO) — One point (std.) and three
more point is optionally available as follows.
Digital output DO1 (std.):
Output type: Transistor open collector
Number of outputs: One point
Output capacity : 30Vdc, 200mA maximum
Digital output DO2~DO4 (opt.)
(Added when 9
th
digit of specification code is “3”)
Out put type: Solidstate relay output (non polarity)
Number of outputs: 3 points
Output capacity: 150Vdc, 150mA maximum or
150Vac (peak to peak),
100mA maximum
DO functions—Four digital output function, either of
the following functions can be selected.
• Totalizer pulse output
DO1 or DO2 can be selected (Forward direction
pulse and reverse direction pulse can be assigned