Kidde Fire Systems VEGA LT TM0081 User Manual

Page of 51
TM0081      
Page 26 of 51
 Issue 1.01
9.4  
SET MENU
The Set menu Table 8 provides the user dependent upon Access level with the following options.
SET – Menu Functions
Sub-Menu 1
Sub- Menu 2
Access
Level 2
Access
Level 3
Function
Time & Date
"
"
Enter revised Time, select AM or PM, 12 hr or 24 hr format
and enter Day/Month/Year and press enter (
) button to
confirm.
Printer Status
Printer type
"
"
Confirms the type of printer currently installed. Standard Dot
Matrix or Thermal type. Note: Vega LT uses Thermal only.
Printer status
"
"
Confirms the current status of the printer – enabled or
disabled.
Select type
"
"
Select type of printer installed – Standard or Thermal and
press enter (
) button to confirm selection.
Select status
"
"
Controls the operation of the printer – Select Enable or
Disable and press enter (
) button to confirm. Note: When
the printer is installed correctly and disabled status is set,
the printer will automatically print priority 0 & 1 events.
Activate day
mode
Day mode status
"
"
Confirms the current day mode status – active or inactive.
Select status
"
"
Controls the operation for day mode – Select Activate or
Deactivate and press enter (
) button to confirm.
Standard features
-
"
Custom features
-
"
Refer to Programming section of this manual.
Clear memory
Zone info
-
"
To clear Fire Zone info  - press enter (
) button to confirm.
Plant info
-
"
To clear Plant Zone info  - press enter (
) button to confirm.
Group info
-
"
To clear Output Group info  - press enter (
) button to
confirm.
Device info
-
"
To clear loop device info  - press enter (
) button to confirm.
BLC outputs
-
"
To clear MBLC info  - press enter (
) button to confirm.
Activations
-
"
To clear Activations info  - press enter (
) button to confirm.
Motherboard info
-
"
N/A
User passwords
Change level 2
-
"
Enter new level 2 pass code ####, Re-enter new level 2
code #### and press enter (
) button to confirm.
Change level 3
-
"
Enter new level 3 new pass code ####, Re-enter new level
3 pass code #### and press enter (
) button to confirm.
Loop config
Accept logon
count
-
"
An option is provided to view new devices added or
removed from the specified detection loop. Select ‘Yes’ and
press enter (
) button to confirm devices accepted.
Accept config
count
-
"
Download configuration device faults. Devices that do not
match the VIPER upload download site file are flagged as a
config fault and are listed.
 Autolearn
-
"
Enables the user to automatically re learn devices for the
specified loop number.
Table 8: Set Menu