Kidde Fire Systems VEGA LT TM0081 User Manual

Page of 51
TM0081      
Page 27 of 51
 Issue 1.01
9.5   
TEST MENU
The Test menu Table 9 provides the user dependent upon Access level with the following options.
Sub-Menu 1
Access
Level 2
Access
Level 3
Function
Panel Test
"
"
Press enter (
) button to initiate a panel LED, LCD display & Buzzer test and MCP
software version installed.
Device Test
-
"
Enter the device parameters to be tested and press enter (
) button to confirm.
Automatic detectors pulse the base alarm LED during the test.
Output group test
-
"
Enter the output group number to be operated and press enter (
) button. WARNING,
ensure that output groups programmed to operate release units are isolated locally.
Press silence alarms button to de-activate the output group and reset to select a new
group to be tested or cancel to return to menus.
Alarm simulation
-
"
Enter the device parameters to be tested and press enter (
) button. WARNING,
Output Groups will operate, ensure that groups programmed to operate release units
are isolated locally. Press silence buzzer, silence alarms & reset buttons to return to
status normal.
Key test
-
"
Press enter (
) button to initiate test and operate fascia key buttons as required. To
exit test option, press the cancel (
) button.
Test mode
-
"
Select activate & press enter (
) button. Enter zone number to be tested & press enter
(
) button. To quit zone test mode, select de-activate & press enter (
) button.
Table 9: Test Menu