3 -  4
3. SIGNALS AND WIRING
3.1.2
Speed control mode
RA1
RA2
RA3
18
10
20
SP1
SG
SG
1
2
3
P24M
P24G
P24L
+
CN1A
15
5
14
8
9
16
17
Plate
20
1
11
EMG
SON
RES
ST1
ST2
LSP
LSN
SD
SG
P15R
SG
LG
10
2
ALM
19
ZSP
6
TLC
15
5
14
7
16
17
4
LZ
LZR
LA
LAR
LB
LBR
LG
OP
P15R
SD
1
6
Plate
CNP1
Servo amplifier
CN1B
(Note1)
CNP2
CNP3
13
Servo
motor
+
8
7
SP2
VC
12
TLA
19
18 SA
RD
RA5
RA4
CN1A
Speed reached
Ready
3
VDD
COM
RA
2m (6.5ft) max.
10m (32ft) max.
Personal
computer
(Note 9)
Servo configuration
software 
Zero speed
Limiting torque
(Note 6)
Trouble
(Note 4,7)
30m (98ft) max.
Forward  rotation stroke end
Forced stop
Servo on
Reset
Speed selection 2 
Reverse rotation stroke end
(Note 3)
(Note 5)
(Note 8) Analog torque limit
+10V/max. current
Encoder Z-phase pulse 
(differential line driver)
Encoder A-phase pulse 
(differential line driver)
Encoder B-phase pulse 
(differential line driver)
Control common
Encoder Z-phase pulse 
(open collector)
(Note 4,7)
CN1B
(Note 4)
(Note 4,7)
Analog speed command
±
10V/Rated speed
Upper limit setting
Upper limit setting
Circuit
protector
Speed Selection 1
24VDC power supply
Forward  rotation start
Reverse rotation start
Note: 1. To prevent an electric shock, fit the supplied earth terminal (E) to the servo amplifier and always
connect it to the earth (E) of the control box. (Refer to section 3.9.)
2. Connect the diode in the correct direction. If it is connected reversely, the servo amplifier will be
faulty and will not output signals, disabling the forced stop and other protective circuits.
3. The forced stop switch must be installed.
4. CN1A and CN1B have the same shape. Wrong connection of the connectors will lead to a fault.
5. When starting operation, always connect the forward/reverse rotation stroke end signal (LSN/LSP)
with SG. (Normally closed contacts)
6. Trouble (ALM) is connected with COM in normal alarm-free condition.
7. The pins with the same signal name are connected in the servo amplifier.
8. TLA can be used by setting any of parameters No. 43 to 48 to make TL available.
9. Use MRZJW3-SETUP61E or later.