Life safety systems  22 
Fire detection system 
Each HP POD 240e NA is equipped with a fire alarm panel that is integrated with the fire detection system. 
The fire system is designed as a stand-alone system, but the system can also interface with customer site fire 
alarm systems. Customer site connections are the responsibility of the customer. Consult with HP for 
connection locations. 
The fire protection system includes: 
 
VESDA air sampling smoke detection system (on page 
) 
 
Manual fire pulls (on page 
) 
 
Fire alarm panel (on page 
) 
 
Fire alarm indicators (on page 
) 
 
VESDA air sampling smoke detection system 
  
 
CAUTION: 
 Excess dust within the HP POD 240e NA can cause the VESDA smoke detector to 
trigger a fire alarm. 
  
The VESDA system features a single zone laser scan early warning smoke detector to provide the earliest 
warning of a potential fire. 
The orange VESDA piping that runs throughout the HP POD 240e NA includes inlets for smoke sampling. The 
VESDA uses a high-efficiency aspirator to continuously draw in air from the HP POD 240e NA and circulate 
the air through a dual-stage filter: 
 
Stage 1—A filter removes dust and dirt from the air sample. 
 
Stage 2—An ultra-fine filter removes remaining contaminants in the air sample. 
After the air passes through the dual-stage filter, it enters a calibrated detection chamber where a laser scans 
the air sample for the presence of smoke. The VESDA system cycles through two levels if smoke is detected: 
 
Level 1—Smoke concentration reaches the first setpoint, and the VESDA system sends an alarm signal 
indicating that a fire might exist. 
 
Level 2—Smoke concentration reaches the second setpoint, and the VESDA system indicates that a fire 
exists in the HP POD 240e NA. 
  
 
IMPORTANT:
  The VESDA filter must be changed regularly to be sure that smoke detection 
readings are accurate. For more information about changing the VESDA filters, see the HP 
Performance Optimized Datacenter 240e NA Maintenance and Service Guide
  
 
Manual fire pulls 
The HP POD 240e NA has six fire pulls; two in each aisle. They are located in the life safety switch cabinet 
next to each personnel door of the HP POD 240e NA. 
Manually activating a fire pull does the following: 
 
Triggers a fire alarm 
 
Activates the fire alarm system horn and strobe lights