Life safety systems  21 
Item  Component 
Indicator color 
Description 
EPO mode 
Key control 
The key control allows you to select the 
EPO mode: 
 
Armed 
 
Test 
 
Bypass 
EPO reset 
White button 
Select to reset the EPO system 
 
 
EPO modes 
The EPO system has three operating modes: 
 
Armed—The EPO system is armed and operational. 
 
Test—The EPO system is in test mode and will not power off the HP POD 240e NA in the events that 
would normally trigger an EPO. 
 
Bypass—The EPO system is non-operational and will not power off the HP POD 240e NA in any events 
that normally trigger an EPO. 
For more information, see "ECS touchscreen and EPO indicators (on page 
)." 
The illuminated external EPO status indicator displays the current EPO mode. 
 
White—The EPO system is armed and operational. 
 
Red—There has been an EPO event and the HP POD 240e NA is shutdown. 
 
Yellow—The EPO system is operating in test mode. 
 
EPO accidental activation 
To help prevent accidentally pressing the EPO button and activating the EPO system, each EPO button is 
covered with a clear Lexan cover. 
 
Battery backup during an EPO event 
The following components are equipped with a UPS to help be sure that service is not interrupted during a 
loss of power to the HP POD 240e NA: 
 
Environmental control system (on page 
 
VESDA air sampling smoke detection system (on page 
) 
 
Fire detection system (on page 
) 
 
Lighting (on page 
) 
  
 
IMPORTANT:
  All critical IT UPS devices with batteries that exceed 700VA must be connected to 
the HP POD 240e NA EPO system, to be sure that the UPS batteries are disconnected during an 
EPO event. For more information about connecting UPS devices to the EPO system, see the HP 
Performance Optimized Datacenter 240e NA Maintenance and Service Guide
.