Life safety systems  20 
 
IMPORTANT:
  The EPO system must be reset before you can power up and restart the HP POD 
240e NA. 
  
To reset the EPO system: 
1. 
Determine and correct the reason for EPO system initiation. 
2. 
If the EPO was triggered manually, the EPO button that was pushed must be reset by rotating the button 
as indicated. 
3. 
Verify the key control for the EPO mode is in the Armed position. 
4. 
Press and release the white EPO reset button. 
 
ECS touchscreen and EPO indicators 
The ECS touchscreen and EPO indicators are located on the IT section A control panel door. 
The touchscreen enables easy configuration of environmental parameters and access data, and also 
monitors environmental, life safety, and security conditions within the HP POD 240e NA. 
The EPO indicators provide the EPO status and enable the EPO system mode to be adjusted. 
 
 
Item  Component 
Indicator color 
Description 
External EPO status 
indicator 
 
White—Normal operating mode 
 
Yellow—Bypass operating mode 
 
Red—EPO shutdown mode 
Indicates the operating status of the HP 
POD 240e NA 
Power on 
White 
Indicates the EPO power status 
EPO shutdown 
Red 
Indicates an EPO shutdown or alarm 
condition 
EPO armed 
White 
Indicates the EPO system is armed and 
operational 
EPO bypass mode 
Yellow 
Indicates the EPO is operating in bypass 
mode 
EPO bypassed 
Green 
Indicates that the EPO functionality and 
shutdown is bypassed