Delta Tau GEO BRICK DRIVE User Manual

Page of 294
 Geo Brick Drive User Manual 
Specifications 
 17 
Environmental Specifications 
Description 
Specifications 
Operating Temperature  
0 to 45°C 
Above 40°C,de-rate current output by 2.5% per °C 
Storage Temperature 
-25°C to +70°C 
Humidity 
10% to 90% non-condensing 
Operating Altitude 
~3300 Feet (1000 m)   
De-rate current output by 1.1% per additional 330 feet (100m) 
Air Flow Clearances 
~3 inches (76.2mm)  above and below unit for air flow  
Operating Environment 
Pollution Degree 2 or equivalent 
 
Protection Specifications 
 
 
Caution 
The  internal  I
2
T  applies  to  and  protects  the  amplifier  power  blocks. 
The  software  I
2
T  (described  in  later  section)  has  to  be  configured 
properly to protect against motor/equipment damage.   
 
Description 
Specifications 
Over Voltage 
~ 283 VAC / 400 VDC 
Under Voltage 
~ 87  VAC / 123 VDC  
Over Temperature 
~ 80
Motor Short Circuit 
500 % of rated peak Amps per axis 
Over Current 
110 % over rated peak Amps per axis 
AC Input Phase Loss Detection 
Loss of one or more phases (3 Phase operation only) 
Shunt Fault Detection 
Integrated, I
2
T model  
Internal I
2
T protection 
2 seconds at peak rated Amps (RMS) per axis 
 
 
Note 
The  under  voltage  fault  triggers  when  the  AC  Input  dips  below  87 
VAC.  However,  if  this  threshold  has  not  been  reached  (i.e.  Low 
Voltage/DC operation) the under voltage logic remains unarmed. 
 
Agency Approvals 
Description 
Specifications 
UL 
UL508C File E307874 
cUL 
CSA C22.2 No. 14-05 File E307874