Bradford-White Corp BWCV User Manual

Page of 44
Internet Version for Reference Only
 
Bradford White
Page 26
Copper Brute II
Page 27
6.3.4  Boiler Maximum (BOIL MAX)
The boiler maximum (BOIL MAX) is the highest 
water temperature that the control is allowed to use 
as a target temperature. If the control does target 
BOIL MAX, and the heater outlet sensor is near the 
BOIL MAX temperature, the MAX segment turns 
on in the LCD while the target, inlet, outlet or supply 
temperature is viewed (see Figure 14).
a set point demand. During WWSD, if the pump has 
not operated at least once every 70 hours, the control 
energizes the terminals for 10 seconds. This minimizes 
the possibility of the pump seizing during a long 
period of inactivity. During External Heater Operation 
(mode 6), the pump contact closes whenever there is a 
heat demand.
Boiler Purge (PUMP DLY) – After a demand 
is satisfied, the control continues to operate the pump 
for a period of time. The length of time that the pump 
continues to run is based on the pump delay setting. 
Once the last stage of the control turns off, the control 
keeps the pump contacts energized for the time 
selected (between 0 and 10 minutes). When OFF is 
selected, there is no purging. When ON is selected, 
pump operation is continuous. Also, during outdoor 
reset, with the pump delay set to ON, the pump 
continues to run even during Warm Weather Shut 
Down.
6.3.7  Set point Operation
When either mode 1 or 2 is selected, the control 
controls the water temperature based on a fixed set 
point. The set point temperature is set using the BOIL 
TARGET item in the Adjust menu.
Heat Demand – For “heat demand” to exist, 
there must be continuity between the Com D (common 
demand) and the Ht D (heat demand) terminals. The 
heater ships with a jumper between these terminals.
The control also evaluates the sensor(s) installed 
in the system, including the outlet sensor provided 
on the heater when using mode 1. When the control 
senses continuity between Com D and Ht D terminals, 
and that the sensor reading is below the target 
temperature, the control will activate the Dem segment 
in the display.
The control energizes the pump (on pump 
mounted heater) and energizes the Pmp Pmp terminals. 
The heater pump segment is turned on in the display. 
The control then operates the stages to maintain the set 
point temperature.
6.3.8  Dedicated Domestic Hot Water
When mode 3 is selected, the control provides 
dedicated domestic hot water operation. 
Internal DHW Demand – A sensor is required 
to be connected on the SC2 and Sup/S terminals. 
An internal demand for DHW is generated when the 
temperature demand for DHW sensor drops 1⁄2 of the 
tank differential setting below the desired DHW tank 
temperature. The TANK TARGET setting is used to 
set the desired DHW tank temperature.
Once an internal demand is generated, the 
Dem segment turns on in the LCD. The control then 
closes the Pmp Pmp contact, which starts the pump 
and the control turns on the heater pump segment in 
the display. The control then operates the stages to 
maintain the programmed heater target temperature at 
the heater outlet sensor. 
Figure 14. Temperature Control Min & Max Graph.
6.3.5  Boiler Target Temperature
The target temperature is determined from 
the mode of operation. The control displays the 
temperature that is currently trying to maintain at 
the operating sensor as BOIL TARGET in the View 
menu. The operating sensor for modes 1, 3 and 4 is the 
outlet sensor (on the heater). The operating sensor for 
modes 2 and 5 is the supply sensor (in the system or 
primary loop). If the control does not presently have 
a requirement for heat, it displays “- - -” in the LCD. 
There is no target temperature generated in mode 6 
(external controller mode).
6.3.6  Pump Operation
The pump terminals (Pmp Pmp) are energized 
with 24 VAC to control a field supplied pump 
contactor. During set point operation (modes 1 and 2), 
the terminals are energized whenever there is a heat 
demand. During dedicated DHW operation (mode 
3), the terminals are energized whenever there is an 
internal heat demand. During outdoor reset (modes 4 
and 5), the terminals are energized whenever there is 
either a heat demand and the control is not in Warm 
Weather Shut Down (WWSD), or whenever there is