Bradford-White Corp BWCV User Manual

Page of 44
Internet Version for Reference Only
 
Bradford White
Page 26
Copper Brute II
Page 27
Minimum Off Time (MIN OFF) – The 
minimum off time is the minimum amount time that a 
stage must be off before it is allowed to turn on. Once 
a stage turns off, it cannot turn on until a minimum 
off time elapses. The minimum off time is adjustable 
through the MIN OFF setting in the Adjust menu.
Proportional & Integral & Derivative (PID) 
– PID staging allows the control to determine when 
the next stage is required to turn on. The control 
automatically determines the settings that are manually 
selected in proportional staging mode. After each stage 
is turned on in the firing sequence, the control waits a 
minimum amount of time before turning on the next 
stage. After the minimum time delay between stages 
has expired, the control examines the control error to 
determine when the next stage is to fire. The control 
error is determined using PID logic.
Proportional compares the actual operating 
sensor temperature to the heater target temperature. 
The colder the temperature, the sooner the next stage 
is turned on.
Integral compares the actual operating sensor 
temperature to the heater target temperature over a 
period of time.
Derivative determines how fast or slow the 
operating sensor temperature is changing. If the 
temperature is increasing slowly, the next stage is 
turned on sooner. If the temperature is increasing 
quickly, the next stage is turned on later, if at all.
Boiler Mass (BOIL MASS) – The boiler mass 
setting allows the installer to adjust the control to the 
thermal mass of different types of heat sources used. 
The boiler mass setting automatically determines the 
interstage differential, interstage delay on, interstage 
delay off, minimum on time and minimum off time of 
the stages when PID staging is used. A higher thermal 
mass setting provides slower staging, while a lower 
thermal mass setting provides faster staging. Copper 
Brute II water heaters are low-mass appliances, and 
therefore, should be used with the lower thermal mass 
setting. Set BOIL MASS to “1”.
6.3.3  Boiler Minimum (BOIL MIN)
The minimum boiler setting (BOIL MIN) is the 
lowest water temperature that the control is allowed 
to use as a target temperature. During mild conditions, 
if the control calculates a target temperature that is 
below this setting, the target temperature is adjusted to 
at least the minimum setting. During this condition, if 
the unit is operating, the MIN segment turns on in the 
LCD while the target temperature or operating sensor 
temperature is viewed. For Copper Brute II units, this 
must be set no lower than 120°F (49°C) to protect the 
unit from condensing on the heat exchanger (see Figure 
14).
6.3.1  Differential
Differential has an abbreviated name of DIFF. An 
on/off heat source must be operated with a differential 
in order to prevent short cycling. The differential 
is divided around the boiler target temperature (see 
Figure 13). The first stage contact will close when the 
water temperature at the operating sensor is one-half of 
the differential setting below the target temperature. It 
will open when the water temperature at the operating 
sensor is one-half of the differential setting above the 
target temperature. The remaining stages will operate 
sequentially, based on the staging mode selected.
6.3.2  Staging Mode
The Copper Brute II 500 and 750 control 
operates two stages. The Copper Brute II 1000 control 
operates three stages. The Copper Brute II control for 
models 1250-2000 operates four stages. The method 
of staging used by the control is either P (proportional) 
or PID (proportional & integral & derivative), and 
is selected using the STGMODE item in the Adjust 
menu.
Proportional (P) – Proportional staging, also 
known as step staging, is based on manually adjusted 
settings which determine when the next stage is 
required to turn on. These manual settings are based 
on temperature and time. The interstage differential 
sets the temperature drop at which the next stage turns 
on. However, in order for a stage to fire, the interstage 
delay on and minimum off times must first elapse.
Interstage Differential (STG DIFF) – The 
interstage differential is the temperature drop at which 
the next stage will turn on. Once a stage turns on, the 
next stage cannot turn on until the temperature drops 
the interstage differential below the temperature at 
which the previous stage turned on. The interstage 
differential is adjustable through the STG DIFF setting 
in the Adjust menu. See Figure 13.
Interstage Delay On (ON DLY) – The 
interstage delay on is the amount of time that must 
elapse before turning on the next stage. Once a stage 
turns on, the next stage cannot turn on until the 
interstage delay on time elapses. The interstage delay 
on is adjustable through the ON DLY setting in the 
Adjust menu.
Interstage Delay Off (OFF DLY) – The 
interstage delay off is the amount of time that must 
elapse before turning off the next stage. Once a stage 
turns off, the next stage cannot turn off until the 
interstage delay off time elapses. The interstage delay 
off is adjustable through the OFF DLY setting in the 
Adjust menu.
Minimum On Time (MIN ON) – The minimum 
on time is the minimum amount time that a stage must 
be on before it is allowed to turn off. Once a stage 
turns on, it cannot turn off until a minimum on time 
elapses. The minimum on time is adjustable through 
the MIN ON setting in the Adjust menu.