Bradford-White Corp BWCV User Manual

Page of 44
Internet Version for Reference Only
 
Bradford White
Page 24
Copper Brute II
Page 25
If the heater is not a pump mounted model, a 
24VAC pump contactor may be connected to the 
“PMP” terminals to control a field installed pump.
Program the temperature control to use “Mode 
2.” The AUTO/MAN switch must be in the AUTO 
position in this mode.
Mode 4:    Hydronic outdoor reset system 
without primary / secondary piping.
Bradford White strongly suggests the use of 
primary secondary piping with the Copper Brute II 
heater. This piping style best ensures that the Copper 
Brute II will have proper water flow. However, non-
primary secondary methods can be used successfully, 
so this section has been included.
Install the outdoor reset sensor, Bradford White 
part number R2014000, and connect the leads to the 
“OD S” and “S C2” terminals.
You must provide an indication of the system’s 
heat demand by removing the jumper across the 
“ComD” and “HtD” terminals on the field wiring 
panel and connecting a zone valve or zone pump end 
switch, thermostat, aquastat or other contact closure to 
these terminals. If the “ComD” and “HtD” terminals 
are left jumpered, the control will always see a heat 
demand and remain in “Dem” mode, with the boiler 
pump running continuously. See Section 5.2 for more 
information.
Reset Override: An additional thermostat or aquastat 
may be connected to the “Set D” and “Com D” 
terminals. A call for heat from either of these controls 
will start the heater’s pump and cause the heater to fire. 
If the heater is not a pump mounted model, a 
24VAC pump contactor may be connected to the 
“PMP” terminals to control a field installed pump.
Program the temperature control to use “Mode 
4.” The AUTO/MAN switch must be in the AUTO 
position in this mode.
Mode 5:    Primary secondary piping with 
outdoor reset.
Install the outdoor reset sensor, Bradford White 
part number R2014000, and connect the leads to 
the “OD S” and “S C2” terminals. Install a “supply 
sensor” in the primary loop using the Bradford White 
part number R2014800 sensor (included with every 
heater). Connect the sensor to the “S C2” and “SUP S” 
terminals. 
You must provide an indication of the system’s 
heat demand by removing the jumper across the 
“ComD” and “HtD” terminals on the field wiring 
panel and connecting a zone valve or zone pump end 
switch, thermostat, aquastat or other contact closure to 
these terminals. If the “ComD” and “HtD” terminals 
are left jumpered, the control will always see a heat 
demand and remain in “Dem” mode, with the heater 
pump running continuously. See Section 5.2 for more 
information.
A secondary aquastat, such as for a separate heat 
exchanger for DHW, can be connected to the “Set D” 
and “Com D” terminals. A call for heat from these 
controls will start the heater pump and cause the heater 
to fire.
If the heater is not a pump mounted model, a 
24VAC pump contactor may be connected to the 
“PMP” terminals to control a field installed pump.
Program the temperature control to use “Mode 
5.” The AUTO/MAN switch must be in the AUTO 
position in this mode.
Mode 6:    Heater with external staging 
control (multiple boiler control, 
building automation system, energy 
management system, etc.)
Leave the jumper installed between “Ht D” and 
“Com D” terminals.  There are terminals on the field 
wiring panel that must be wired per the instructions 
in section 5.3 of this manual.  Other wiring methods 
may be unsafe.  The wiring in section 5.3 of this 
manual must be used.
The AUTO/MAN switch is located on the circuit 
board in the slide-out control panel on the front of the 
heater.  This switch is placed in the manual position 
(MAN) when an external control is controlling the 
heater stages.
Program the temperature control to use Mode 6.  
Mode 6 tells the heater control that an external staging 
control is being used.
6.3  Advanced Topics
    For most installations, section 6.2 provides all 
the information required to set up the Copper Brute II 
heater, and this section should be skipped. Continue 
setup in section 6.4.
This section provides definitions of the 
programming parameters, advanced programming 
topics, and other information that may be of interest.
Advanced programming mode allows the 
installer to set the temperature control for proportional 
staging. In advanced programming mode, the 
interstage differential, interstage delay, interstage on 
and off delay, and minimum time on and off are all set 
manually.
NOTE: Advanced programming mode is not required 
in most applications, and is intended for advanced 
installers only. 
To enter advanced programming mode, remove 
the bezel on the temperature control by pulling out at 
the bottom. Remove the small Phillips head screw to 
access the dip switch. The dip switch is mounted on 
a circuit board. Locate the letter “A” on the circuit 
board and slide the corresponding dip switch toward 
the letter “A”. The default setting of this dip switch is 
toward the “OFF” lettering on the circuit board.