 D7024 
 Panel 
Programming 
 
 
D7024 Operation and Installation Guide 
 
© 2005 Bosch Security Systems 
Page 65 
41740F 
7.6.2.2 Dialing 
Type
 
 
Shortcut: 0-
PROG
, 6-
PROG ACC’NTS
, 2-
PHONE CONTROL
 
This feature determines what format the panel will use for dialing on each phone line. The tone/pulse setting will first try 
tone dialing, and if that fails, will switch to pulse dialing. 
Choose Line 1 or Line 2. The display will scroll through the Phone Control options. Press [2] for DIALING TYPE. The 
following window will display: 
PHONE CONTRO (__) 
1-  
PULSE ONLY 
2-  
TONE/PULSE 
3-  
TONE ONLY 
Press the number key that corresponds to your selection. The previous window will be displayed. 
7.6.3 Report 
Steering 
 
Shortcut: 0-
PROG
, 6-
PROG ACC’NTS
, 3-
RPT STEERING
 
Different classes of reports can be directed to different phone numbers.  Non-supervisory alarms include fire alarms, 
waterflow alarms and monitor alarms.  Supervisory alarms come from points configured as a supervisory type.  Non-
supervisory restorals include fire, waterflow and monitor restorals. Supervisory restorals come only from points configured 
as a supervisory type.  Trouble reports include all point and system troubles and restorals.  Tests include auto tests, 
manual tests and off-normal at test reports.  The panel allows the special reports “silence”, “reset” and “drill” to be 
individually directed. 
 
If any reports are steered to Phone Number 2 (including the default, “phone 2 backup”), a phone 
number and account number must be programmed for Phone Number 2. The panel will indicate a 
“comm fault” if it sends a report (using phone number 1 parameters) which references 
unprogrammed Phone Number 2 parameters. 
The display will scroll through the following items: 
REPORT STEERING 
1-  
NONSUP ALRM 
2-  
SUPVSRY ALRM 
3-  
NONSUP RSTR 
4-  
SUPVSRY RSTR 
5-  
TROUBLE 
6-  
TESTS 
7-  
SILENCE 
8-  
RESET 
9-  
FIRE DRILLS 
Press the number key that corresponds to your selection. The following window will display (with varying headings, 
depending on your choice. In this example, non-supervisory alarm is selected): 
NONSUP ALRM (___) 
1-  
PHONE 1 ONLY 
2-  
PHONE 2 ONLY 
3-  
PHON 1 AND 2 
4-  
PHN 2 BACKUP 
5-  
NO REPORT 
 
PHONE 1 ONLY:
 Report sent to Phone #1 only. 
 
PHONE 2 ONLY:
 Report sent to Phone #2 only. 
 
PHONE 1 AND 2:
 Report sent to Phone Numbers 1 and 2. 
 
PHONE 2 BACKUP:
 Report sent to Phone #1, then to Phone #2 if #1 fails. 
 
NO REPORT:
 No report sent. 
Press the number key that corresponds with your selection. The previous window will be displayed.