Bosch Appliances Network Router D6100 User Manual

Page of 168
Conettix D6600/D6100 | Computer Interface Manual | 3.0  
Computer Communication Protocols 
 
Bosch Security Systems, Inc. | 1/07 | 4998122703-01 
41 
 
 
Figure 19:  Message sent to printer 
mm/ddshh:mmsLxxsSCNsACCTsaaaaaa+++sACC
saaaaaasCCCCsCCCCsCCCCsCCCCsC 
 
 
For lines that are grouped, Gxx appears 
instead of Lxx. 
 
 
Table 67: 
Scancom 4-16-1, 5-16-1, 6-16-1 - 
Available Upon Request (Message 
Type g) Printer Output 
 
Characters Description 
SCN 
Scancom. 
Lxx: Line 
number. 
Gxx 
Grouped line numbers. 
 
 
3.2.18  Scancom 4-24-1, 5-24-1, 6-24-1 - Available Upon Request (Message Type h) 
SIA Mode Description 
4-24-1 Example 
<LF><CRC><h><sequence#><receiver#><line#>[#aaaaaa|CCCCsCCCCs 
CCCCs CCCCsCCCCsCCCCsC]<CR> 
 
Table 68: 
Scancom 4-24-1, 5-24-1, 6-24-1 - Available Upon Request (Message Type h) Byte Description  
 
Title Description 
LF 
Standard line feed character.  
CRC 
Cyclical redundancy check number.  
Message Type 
h  
sequence# 
The message sequence number. The valid sequence number range is 0001 to 9999.  
receiver# 
The receiver gateway that sent the message. Valid digits are 01 to 99 for D6600/D6100.  
line# 
(Line/Group #) 
The line number of the line in the receiver gateway that sent the message. Valid digits are 00 to 
99. The receiver uses Line 0 (zero) for internal messages.  
account# 
The communicator's account number, up to six digits. 
CCCC 
Channels 1 to 4.  
One space.   
CCCC 
Channels 5 to 8.  
One space.   
CCCC 
Channels 9 to 12.  
One space.   
CCCC 
Channels 13 to 16.  
One space.   
CCCC 
Channels 17 to 20.  
One space.   
CCCC 
Channels 21 to 24.  
One space.   
Supervisory channel.   
 
 
Figure 20:  Message sent to printer 
mm/ddshh:mmsLxxsSCNsACCTsaaaaaa 
+++sACCsaaaasCCCCsCCCCsCCCCsCCCC 
++++++++++++++CCCCsCCCCsC 
 
 
For lines that are grouped, Gxx appears 
instead of Lxx. 
 
 
Table 69: 
Scancom 4-24-1, 5-24-1, 6-24-1 - 
Available Upon Request (Message 
Type h) Printer Output 
 
Characters Description 
SCN 
Scancom. 
Lxx: Line 
number. 
Gxx 