3.2.25  Silent Knight FSK80 (Message Type E) 
SIA Mode Description 
Silent Knight 
FSK80 Example 
<LF><CRC><E><sequence#><receiver#><line#>[#AAAA|NBAXY]<CR> 
 
Table 79: 
Silent Knight FSK80 (Message Type E) Byte Description 
 
Title Description 
LF 
Standard line feed character.  
CRC 
Cyclical redundancy check number.  
Message Type 
sequence# 
The message sequence number. The valid sequence number range is 0001 to 9999. 
receiver# 
The receiver gateway that sent the message. Valid digits: 01 to 99 for D6600/D6100. 
line# 
(Line/Group #) 
The line number of the line in the receiver gateway that sent the message. Valid digits: 00 to 
99. The receiver uses Line 0 (zero) for internal messages. 
account # 
The communicator's account number has four digits. 
NBA 
Alarm event 
 
 
Figure 22:  Message sent to printer 
MM/DDsHH:MMsLxxsSFKsACCTsAAAA 
+++ACCTsAAAAsALARM_ZNs1 
+++ACCTsAAAAsALARM_ZNs2 
+++ACCTsAAAAsALARM_ZNs3 
+++ACCTsAAAAsALARM_ZNs4 
+++ACCTsAAAAsALARM_ZNs5 
+++ACCTsAAAAsALARM_ZNs7 
+++ACCTsAAAAsALARM_ZNs8 
+++ACCTsAAAAsALARM_ZNs9
 
 
 
Table 80: 
Silent Knight FSK80 Printer/LCD 
output 
 
Characters Description 
MM/DDsHH:MM 
Date and time. 
SFK SFSK80 
format. 
Lxx 
Line number. 
AAAA The 
communicator's account number 
has four digits.  
Space.