D9412GV2/D7412GV2 | Operation and Installation Guide | Appendix A: System Wiring Diagrams, Issue A
.
Bosch Security Systems, Inc. | 5/05 | F01U003641B
65
Figure 35: D9412GV2, Input Points and Peripheral Devices
P105BL
D125B
Sw. Aux Pwr
Zone B
Zone A
Pnl Common
Pnl Common
Loop B-
Loop A-
Loop B+
Loop A+
Earth Ground
10
9
5
4
3
8
2
1
7
6
D129
Aux Power
Zone B
Zone A
Common
Loop B-
Loop A-
Loop B+
Loop A+
Earth Ground
10
9
5
4
3
8
2
1
7
6
11
12
13
Loop A+
Loop A-
Loop B+
Loop B-
P105F
EARTH GROUND
COMMON
BATTERY NEGATIVE ONLY
Maximum Charging
Current 1.4 Amps.
BATTERY POSITIVE ONLY
RELAY A
RELAY B
RELAY C
+ AUX POWER
1
2
3
4
5
6
7
8
9
10
CLASS 2 TRANSFORMER
16.5 VAC 40 VA 60 Hz
Model D1640
Internally Fused - Do Not short
Requires Unswitched Outlet
Do Not Share With Other Equipment
16.5 VAC 40 VA 60 Hz
Model D1640
Internally Fused - Do Not short
Requires Unswitched Outlet
Do Not Share With Other Equipment
PROGRAMMABLE
ALARM OUTPUTS
ALARM OUTPUTS
Terminals
Requires Optional
Model D136 Relay
Model D136 Relay
In ALT ALARM
& SW AUX
&
7
8
GROUND FAULT DETECT
Enabled
Disabled
Disabled
VOLTAGE RANGES
Open
3.7 - 5.0 VDC
Normal
2.0 - 3.0 VDC
Short
0.0 - 1.3 VDC
12
11
13
Point 1 Point 2
15
14
16
Point 3 Point 4
18
17
19
Point 5 Point 6
21
20
22
Point 7 Point 8
+
-
D130
D9412GV2
PHONE
LED
LED
RED
ON when
communicating
OFF when idle
communicating
OFF when idle
PHONE LINE SEIZED
TIP
RING
TELCO
RING
TIP
PHONE LINE
SEIZED
SEIZED
TELCO CORD
MODEL D161
MODEL D161
GRN
D5200/D5360
PROG CONN
PROG CONN
Point 8
S3 Option
S3 Option
Closed = 1K
Ω
EOL
Normal Operation
Open =AB-12 UL
Bell Box 220 K
Bell Box 220 K
Ω
1 - (Optional): For 24 V applications use a UL Listed
24 VDC power supply with a D130 Relay Module.
Refer to the D130 Installation Instructions
(P/N: 74-06262-00) for correct wiring
requirements.
Refer to the D130 Installation Instructions
(P/N: 74-06262-00) for correct wiring
requirements.
2 - To UL Listed two-wire smoke detectors. Refer to
the 9000/G/GV2 Series Technical Service Note:
UL Smoke Detector Compatibility (P/N: 33284) for
a listing of compatible two-wire smoke detectors.
UL Smoke Detector Compatibility (P/N: 33284) for
a listing of compatible two-wire smoke detectors.
3 - P105 1 k
Ω
EOLR (P/N: 14-03130-004): Suitable
for non-powered initiating and supervisory devices
such as pull stations, heat sensors, and valve
tampers.
such as pull stations, heat sensors, and valve
tampers.
4- P105BL1
1k
Ω
EOLR (P/N: 14-0130-004): For
typical burglar alarm applications.
5 - D129 provides optional Waterflow Retard
feature. Not suitable for two-wire smoke
detectors. (Note: Use Zero Retard except for
waterflow devices.)
detectors. (Note: Use Zero Retard except for
waterflow devices.)
All external connections except Terminal 5 (battery positive) are power limited.