Bosch Appliances Video Game Controller D9412GV2 User Manual

Page of 158
D9412GV2/D7412GV2 | Program Entry Guide | 6.0  GV2AUX 
EN | 130 
 
 
Bosch Security Systems, Inc. | 10/08 | F01U003636-04 
 
RPS IP Address 1 
RPS Port Number 
Default: 
Default: 
7700 
Selection:  0 to 255 
Selection:  1 to 65535 
Enter the first three digits of the IP 
address. Leading zeros are not 
required. 
0 to 255 
This prompt specifies the destination port for 
outgoing RPS session requests to the IP address 
specified in RPS IP Address #.  
6.4.2  Using an External Modem 
This prompt and the next three prompts determine 
the IP address for RPS. 
Through the use of a standard, off-the-shelf modem 
(capable of communicating at 9600 baud) and a 
D9133DC connected directly to the control panel, 
RPS can communicate with a D9412GV2 or 
D7412GV2 at speeds of up to 9600 baud.  
An IP address has four fields. Each field has a range 
of 0 to 255. For example, an IP address is expressed 
as 110.227.64.190. (Refer to igure 7.) The D5200 
programmer divides the IP Address into four 
programmable fields. Contact your network 
administrator to determine the IP address to which 
the RPS computer is connected. 
 
igure 7: RPS IP Address Prompts 
 
 
 
 
Set RPS IP Address to 0 if Enable Ext 
Modem
 is set to Yes
RPS IP Address 2 
Default: 
Selection: 
0 to 255 
Refer to RPS IP Address 1
RPS IP Address 3 
Default: 
Selection: 
0 to 255 
Refer to RPS IP Address 1
RPS IP Address 4 
Default: 
Selection: 
0 to 255 
Refer to RPS IP Address 1
Both the U.S.Robotics V.92 56 K Modem 
(model No. 5686, includes V.92 and V.90 
56 K standard technology) and the Best 
 
Data Smart One V.92/V.44 56 K External 
Data/Fax Modem (model # 56SX-92) are 
recommended for use as external 
modems (connected to the control panel) 
based on compatibility testing by Bosch 
Security Systems, Inc. Other modules 
were not tested or were incompatible. 
110.227.64.190
 
RPS IP Address 1
 
RPS IP Address 2
 
RPS IP Address 3
 
RPS IP Address 4
 
The seven prompts on page 134 help to configure the 
requirements necessary to connect an external 
modem to a D9412GV2 or D7412GV2 Control Panel 
using a D9133DC. This configuration allows 
communication with RPS at 9600 baud because data 
is routed through the SDI bus. 
 
Use a separate phone line if an external 
modem is being connected to the control 
panel by a D9133DC Direct Connect 
 
Programming Module. If obtaining a 
different phone line from the line used by 
the control panel is impossible, ensure 
that the control panel is wired in front of 
any premises phone and the external 
modem devices so that full line seizure is 
maintained. Also, ensure that the 
following items are programmed in 
Section 2.7 RPS Parameters on page 32: 
•  Answer Armed = Blank or 0 
•  Answer Disarmed = Blank or 0 
•  RPS Line Monitor = No 
•  RPS Call Back = No 
•  RPS Phone number = Blank