D9412GV2/D7412GV2 | Program Entry Guide | 7.0  RADXAXS 
EN | 147 
 
 
Bosch Security Systems, Inc. | 10/08 | F01U003636-04 
 
D# Buzz Time 
7.2 Strike 
Profile 
This programming category is used to create a 
specific door profile for: 
Default: 
2 sec 
Selection: 
Blank, 1 sec to 240 sec 
 
• 
• 
• 
Strike and shunt times. 
Buzz Time is not programmed for 
this door. 
Blank 
Extending strike and shunt times if a door is left 
open. 
The buzzer sounds for the amount 
of time programmed. 
1 to 240 
Resetting the strike when the door opens. 
Door # 
Enter the amount of time the buzzer output sounds to 
notify the user that the strike was activated and the 
door is ready to open. The buzzer stops as soon as 
the door is opened. 
Default: 
Selection: 
1 to 8 
Enter the door you are programming. 
D# Strike Time 
Default: 
10 sec 
Selection: 
1 sec to 240 sec 
Blank 
Strike Time is not programmed for 
this door. 
1 to 240 
The strike activates for the amount 
of time programmed. 
Enter the amount of time the door controller toggles 
the relay output to activate the door strike. When the 
door strike is activated, the user can open the door. 
The strike activates for a valid token, RTE, REX, and 
the keypad CYCLE DOOR? function. 
D# Shunt Time 
Default: 
10 sec 
Selection: 
Blank, 1 sec to 240 sec 
Blank 
Shunt Time is not programmed for 
this door. 
1 to 240 
The shunt activates for the amount 
of time programmed. 
Enter the amount of time that the Door point is 
shunted to allow a user to open the door. The 
duration of time should be sufficient so that the 
opened door does not cause the point to enter into a 
trouble, alarm, or faulted condition. 
A separate buzzer is required. Many 
readers have an internal buzzer that is 
not affected by Buzz Time. 
 
D# Extend Time 
Default: 
10 
Selection: 
Blank, 1 sec to 30 sec 
Enter the amount of time that strike, buzz, and shunt 
activation is prolonged if a door is left open and the 
shunt time expires. At the end of the programmed 
extend time, the buzzer continues to buzz until the 
door closes. If programmed, the point assigned to the 
door indicates a trouble, alarm, or fault at the keypad. 
The CLOSE DOOR # display on keypad 
does not activate if no time (blank) is 
programmed. 
 
 
Regardless of how the Door point is 
programmed, the system generates a 
Trouble Door Left Open Event while the 
 
system is disarmed, and an Alarm Door 
Left Open Event if the system is armed 
and the door is held open beyond Extend 
Time. Door Closed - Restoral Events are 
generated after the door is held open 
past Extend Time and the door returns to 
normal.