White Rodgers 1E78-144 White-Rodgers 70 Series Non-Programmable Single Stage Thermostat Installation Instruction

Page of 8
www.white-rodgers.com
ELECTRICAL DATA
Electrical Rating: 
 
0 to 30 VAC 50/60 Hz. or D.C. 
 
0.05 to 1.0 Amps (Load per terminal) 
 
1.5 Amps Maximum Total Load (All terminals combined)
THERMAL DATA
Setpoint Temperature Range:
 
 
 
45°F to 90°F (7°C to 32°C) 
Operating Ambient Temperature Range: 
 
32°F to 105°F 
Operating Humidity Range: 
 
0 to 90% RH (non-condensing) 
Shipping Temperature Range: 
 
-40°F to 150°F
Reset Operation
If a voltage spike or static discharge blanks out the display or causes 
erratic thermostat operation you can reset the thermostat by pressing 
 and 
 at the same time while moving the SYSTEM switch from 
OFF to HEAT. This also resets the factory defaults. If the thermostat 
has power, has been reset and still does not function correctly contact 
your heating/cooling service person or place of purchase.
Batteries
For optimum performance, we recommend replacing batteries once 
a year with fresh “AAA” Energizer
®
 alkaline batteries.
6
  SPECIFICATIONS
7
  TROUBLESHOOTING
Symptom
Possible Cause
Corrective Action
No Heat/No Cool/No Fan
(common problems)
Blown fuse or tripped circuit breaker. 
1. 
Furnace power switch to OFF.
2. 
Furnace blower compartment door or  panel 
3. 
loose or not properly installed.
Replace fuse or reset breaker.
Turn switch to ON.
Replace door panel in proper position to engage 
safety interlock or door switch. 
No Heat
Pilot light not lit.  
1. 
SYSTEM Switch not set to 
2. 
HEAT
Loose connection to thermostat or system. 
3. 
Furnace Lock-Out Condition. Heat may also be 
4. 
intermittent. 
 
 
5.  Heating system requires service or thermostat 
requires replacement.
Re-light pilot.
Set SYSTEM Switch to 
HEAT and raise setpoint 
temperature above room temperature.
Verify thermostat and system wires are securely 
attached.
Many furnaces have safety devices that shut   
down when a lock-out condition occurs. If the  
heat works intermittently contact the furnace  
manufacturer or local service person for  
assistance.
Diagnostic: Set SYSTEM Switch to 
HEAT and 
raise the setpoint above room temperature. Within 
a few seconds the thermostat should make a soft 
click sound. This sound usually indicates the ther-
mostat is operating properly. If the thermostat does  
not click, try the reset operation listed above. If the  
thermostat does not click after being reset contact  
your heating and cooling service person or place  
of purchase for a replacement. If the thermostat   
clicks, contact the furnace manufacturer or a  
 
service person to verify the heating is operating    
correctly.
No Cool
SYSTEM Switch not set to COOL. 
1. 
Loose connection to thermostat or system. 
2. 
Cooling system requires service or thermostat 
3. 
requires replacement.
Set SYSTEM Switch to 
COOL and lower  setpoint  
temperature below room temperature.
Verify thermostat and system wires are securely    
attached.
Same procedure as diagnostic for No Heat  
 
condition except set the thermostat to 
COOL and   
lower the setpoint below the room temperature.    
There may be up to a five minute delay before the  
thermostat clicks in Cooling.