3.  
Add the BTU/Hr of all fuel burning appliances in the space. 
 
 
Vent-Free Heater                       _________________________BTU/Hr. 
 
 
Gas Water Heater*                    _________________________BTU/Hr. 
  
 
Gas Furnace                               _________________________BTU/Hr. 
 
 
Vented Gas Heater                     _________________________BTU/Hr. 
    
 
Gas Fireplace Logs                     _________________________BTU/Hr. 
 
 
Other Gas Appliance*              +_________________________BTU/Hr. 
 
 
Total                                         = _________________________BTU/Hr. 
 
 
 
Example: 
Gas water heater 
 
40000  BTU/Hr. 
    Vent-free 
heater + 
18000 
BTU/Hr. 
    Total 
  = 
58000 
BTU/Hr. 
 
 
 
* Does not include direct-vent gas appliances.  Direct-vent draws combustion 
 
 
   air from the outdoors and vents to the outdoors. 
 
 
4.    
Compare the maximum BTU/Hr the space can support with the actual amount 
  of 
BTU/Hr 
used. 
 
 
 
 
   _____________BTU/Hr (maximum the space can support) 
 
 
 
 
   _____________BTU/Hr (actual amount of BTU/Hr used) 
 
 
Example: 
   51200 BTU/Hr (maximum the space can support)  
 
 
 
 
   58000 BTU/Hr (actual amount of BTU/Hr used) 
 
The space in the above example is a confined space because the actual BTU/Hr used is more than the 
maximum BTU/Hr the space can support.  Additional fresh air must be provided.  The following 
options are available. 
A.  Rework worksheet, adding the space of an adjoining room.  If the extra space provides an     
unconfined space, remove door to adjoining room or add ventilation grills between rooms.  See 
“Ventilation Air From Inside Building”, page 15. 
 
B.  Vent room directly to the outdoors.  See “Ventilation Air From Outdoors” page 16. 
 
C.  Install a lower BTU/Hr heater, if lower BTU/Hr size makes room unconfined. 
 
If the actual BTU/Hr used is less than the maximum BTU/Hr the space can support, the space is 
unconfined.  You will need no additional fresh air ventilation. 
 
 
 
WARNING 
 
YOU MUST PROVIDE ADDITIONAL VENTILATION AIR IN A CONFINED SPACE 
 
14