Figure 7       Ventilation Air From Outdoors 
 
WARNING 
 
THIS HEATER MUST HAVE FRESH AIR FOR PROPER OPERATION.  IF NOT, POOR 
FUEL COMBUSTION COULD RESULT.  READ THE FOLLOWING INSTRUCTIONS TO 
ENSURE PROPER FRESH AIR FOR THIS AND OTHER FUEL-BURNING APPLIANCES 
IN YOUR HOME. 
VENTILATION AIR FROM OUTDOORS 
 
Provide extra fresh air by using ventilation grills or ducts.  You must provide two permanent 
openings: one within 12" of the ceiling and one within 12" of the floor.  Connect these items directly 
to the outdoors.  These spaces include attics and crawl spaces.  Follow the National Fuel Gas Code 
NFPA 54/ANSI Z223.1, Section 4.3, “Air For Combustion and Ventilation” for required size of 
ventilation grills or ducts. 
 
IMPORTANT:  Do not provide openings for inlet air into attic if attic has a thermostat-controlled 
power vent.  Heated air entering the attic will activate the power unit. 
Ventilated Attic
Outlet Air
Inlet Air
Ventilated
Crawl Space
To
Crawl
Space
To Attic
Outlet Air
Inlet Air