VENTILATION AIR 
 
VENTILATION AIR FROM INSIDE BUILDING 
This fresh air would come from an adjoining unconfined space.  When venting to an adjoining space, 
you must provide two permanent openings:  one within 12" of the ceiling  and one within 12" of the 
floor on the wall connecting the two spaces (see Options 1 and 2, Figure 6).  You can also remove door 
into adjoining room (see Option 3, Figure 6). 
 
WARNING 
 
REWORK WORKSHEET, ADDING THE SPACE OF THE ADJOINING UNCONFINED 
SPACE.  THE COMBINED SPACES MUST HAVE ENOUGH FRESH AIR TO SUPPLY ALL 
APPLIANCES IN BOTH SPACES. 
 
 
NOTE:  
 Each opening shall have a minimum free area of 1 square inch per 1000 BTU’s per 
hour of the total input ratings of all gas utilization equipment in the confined space, but not less 
than 100 square inches. 
Figure 6   
Ventilation Air From Inside Building 