Sensor Based Thermal Specification Design Guidance
58
Thermal/Mechanical Specifications and Design Guidelines
7.3.2
Thermal Design and Modelling
Based on the boundary conditions the designer can now make the design selection of 
the thermal solution components. The major components that can be mixed are the 
fan, fin geometry, heat pipe or air duct design. There are cost and acoustic trade-offs 
the customer can make.
7.3.3
Thermal Solution Validation
7.3.3.1
Test for Compliance with the TTV Thermal Profile
This step is the same as previously suggested for prior products. The thermal solution 
is mounted on a test fixture with the TTV and tested at the following conditions:
• TTV is powered to the TDP condition 
• Maximum airflow through heatsink
• T
AMBIENT
 at the boundary condition from 
The following data is collected: TTV power, TTV T
CASE
, and T
AMBIENT
. This is used to 
calculate Ψ
CA
 which is defined as:
Ψ
CA
 = (TTV T
CASE
 – T
AMBIENT
) / Power
This testing is best conducted on a bench to eliminate as many variables as possible 
when assessing the thermal solution performance. The boundary condition analysis as 
described in 
 should help in making the bench test simpler to perform.
7.3.3.2
Thermal Solution Characterization for Fan Speed Control
The final step in thermal solution validation is to establish the thermal solution 
performance,Ψ
CA
 and acoustics as a function of fan speed. This data is necessary to 
allow the fan speed control algorithm developer to program the device. It also is 
needed to asses the expected acoustic impact of the processor thermal solution in the 
system.
The fan speed control device may modulate the thermal solution fan speed (RPM) by 
one of two methods. The first and preferred is pulse width modulation (PWM) signal 
compliant with the 4-Wire Pulse Width Modulation (PWM) Controlled Fans specification. 
the alternative is varying the input voltage to the fan. As a result the characterization 
data needs to also correlate the RPM to PWM or voltage to the thermal solution fan. The 
fan speed algorithm developer needs to associate the output command from the fan 
speed control device with the required thermal solution performance. Regardless of 
which control method is used, the term RPM will be used to indicate required fan speed 
in the rest of this document.
7.4
Fan Speed Control (FSC) design process
The next step is to incorporate the thermal solution characterization data into the 
algorithms for the device controlling the fans.
As a reminder, the requirements are: 
• When the DTS value is at or below T
CONTROL
, the fans can be slowed down — just 
as with prior processors.