Sensor Based Thermal Specification Design Guidance
56
Thermal/Mechanical Specifications and Design Guidelines
In the prior thermal specifications this region, DTS values greater than T
CONTROL
, was 
defined by the processor thermal profile. This required the user to estimate the 
processor power and case temperature. Neither of these two data points are accessible 
in real time for the fan speed control system. As a result the designer had to assume 
the worst case T
AMBIENT
 and drive the fans to accommodate that boundary condition.
7.3
Thermal Solution Design Process
Thermal solution design guidance for this specification is the same as with previous 
products. The initial design needs to take into account the target market and overall 
product requirements for the system. This can be broken down into several steps:
• Boundary condition definition 
• Thermal design / modelling 
• Thermal  t
esting