There are four Route Groups which contain a 
selection of event categorizes and individual events. 
Each group has a primary and a backup device. The 
primary device is the first (most important) destination 
used to reach the programmed route within this 
group. The backup device is used if the primary 
device fails. 
 R# Primary Device 
Default: 
No Device 
Selection: 
No Device, Phone 1..4, SDI ## 
Path 1..4 
Phone 1 
Phone 1 is this group’s primary 
destination. 
Phone 2 
Phone 2 is this group’s primary 
destination. 
Phone 3 
Phone 3 is this group’s primary 
destination. 
Phone 4 
Phone 4 is this group’s primary 
destination. 
SDI 88 Path 1 
Path 1 on SDI 88 is this group's 
primary destination. 
SDI 88 Path 2 
Path 2 on SDI 88 is this group's 
primary destination. 
SDI 88 Path 3 
Path 3 on SDI 88 is this group's 
primary destination. 
SDI 88 Path 4 
Path 4 on SDI 88 is this group's 
primary destination. 
SDI 92 Path 1 
Path 1 on SDI 92 is this group's 
primary destination. 
SDI 92 Path 2 
Path 2 on SDI 92 is this group's 
primary destination. 
SDI 92 Path 3 
Path 3 on SDI 92 is this group's 
primary destination. 
SDI 92 Path 4 
Path 4 on SDI 92 is this group's 
primary destination. 
 
 
To meet UL 864 requirements for 
Central Station and Remote Station 
applications, program a Primary 
Device
 
Select the communication device and the primary 
destination. 
Refer to Section 5.5 
Programming Path Numbers 
and IP Addresses for Enhanced Communications on 
page on page 131 to enable enhanced 
communication paths. 
Keypad Programming of R# Primary Device 
D1255 
1.  Refer to Figure 1 on page 7 to access Keypad 
Programming and navigate to the 
ROUTE GRP 1 - 4 option. 
2.  At the ROUTE GRP 1 - 4 prompt, enter the route 
group number you wish to configure and press 
[ENT]. The keypad reads RT GRP 1 PRIMARY
and then the current configuration (for example, 
SDI 88 PATH 4). 
3.  To change the configuration, press [ENT] when 
the current configuration shows, and then press 
[NEXT] or [PREV] to scroll through the options, as 
listed in R# Primary Device on page 19.  
4.  When the keypad reads the desired configuration 
option, press [ENT] to select it. 
When the keypad reads PARAMETER SAVED
your selection has been configured. 
 
D1260 
1.  Refer to Figure 2 on page 8 to access Keypad 
Programming and navigate to the 
Route Group 1 - 4 option. 
2.  At the Route Group 1 - 4 prompt, enter the route 
group number you wish to configure and press 
[ENTER]. The keypad reads Rt Group 1 Primary
and then the current configuration (for example, 
SDI 88 PATH 4). 
3.  To change the configuration, press the Edit 
softkey, and then press the Next or the Previous 
softkey to scroll through the options, as listed in 
R# Primary Device on page 19.  
4.  When the keypad reads the desired configuration 
option, press the Save softkey to select it. 
When the keypad reads Parameter Saved, your 
selection has been configured.