D9412GV3/D7412GV3 | Program Entry Guide | 2.0  Panel and Area Wide Parameters 
EN | 49 
 
 
Bosch Security Systems, Inc. | 10/11 | F01U170807-02 
 
Parameter Setup Requirement: 
The Early Ambush timer can be started and stopped 
only by passcodes with the L## Passcode Disarm 
authority. 
 
To avoid unintended results for the end 
user of the system: 
  When a keypad is assigned to an area 
that has the Early Ambush feature 
enabled, set the CC# Scope value to 
Area Wide. 
  If an area has A# Two Man Rule set 
to Yes, do not set A# Early Ambush 
to Yes
During an alarm, after the first passcode is entered, 
the Early Ambush timer still begins. A Cancel Report 
might be generated, depending upon the bell time, 
and the keypad displays Alarm Silenced normally. If 
the second valid disarm passcode is entered, the 
keypads indicate that the second passcode is valid. 
Refer to the Secondary Ambush Code prompt on 
page 137 for information about the unique behavior 
of the two passcodes. 
For SIA CP-01 Compliance: 
 
This feature is not allowed for use with 
SIA CP-01 compliant installations. 
A# Exit Restart 
Default: 
Yes 
Selection:  Yes or No 
Yes 
Delay armed points in this area 
restart the exit delay timer if violated 
during the exit delay time. 
No 
Delay armed points continue to count 
down normally if violated during the 
exit delay time. 
 
 
This feature must be disabled for UL Line 
Security/Encryption applications. 
When enabled, this feature activates when a 
controlled point with delay alarm response changes 
from normal to faulted and back to normal during the 
exit delay. When activated, if any controlled point in 
the same area with delay alarm response is faulted, 
the exit delay time restarts. The exit delay continues 
until it expires or the area changes arming states. 
This operation can occur only once in an arming 
cycle. 
 
To avoid the possibility of false alarms in 
Associate areas, do not use the A# Exit 
Restart
 feature in areas with A# Area 
Type
 set to Shared
For SIA CP-01 Compliance 
This prompt can be set to Yes or No
A# Arm No Exit 
Default: 
Yes 
Selection: 
Yes or No 
Yes 
Switch the arming state to Perimeter 
if no Perimeter Delay point faults 
occurred. 
No 
Keep the area in Master Arm if no 
Perimeter Delay point faults 
occurred. 
This parameter switches the arming state of an area 
from Master Armed to Perimeter Armed if no 
perimeter points with delay response were activated 
during the exit delay time. Only the final armed state 
is  reported and displayed at the keypads. 
 
The A# Arm No Exit feature does not 
operate in areas with A# Area Type set 
to Shared
For SIA CP-01 Compliance: 
A# Exit Restart
 can be set to Yes or No
A# Exit Warning 
Default: 
Yes 
Selection:  Yes or No 
Yes 
Pulse the alarm output for the last 10 
sec of the Exit Delay time. 
No 
Do not pulse the Alarm Bell output 
during the Exit Delay time. 
When enabled, the Alarm Bell output pulses on and 
off every 2 sec for the remaining 10 sec of the Exit 
Delay time. 
For SIA CP-01 Compliance 
A# Exit Warning
 must be set to Yes