D9412GV3/D7412GV3 | Program Entry Guide | 3.0  Points 
EN | 92 
 
 
Bosch Security Systems, Inc. | 10/11 | F01U170807-02 
 
P## Pt Response 
Default: 
Refer to the program record sheet 
Selection:  0 to F 
Controlled (Non-24-Hour Points) 
Point 
Response  0 1 2 3 4 5 6 7 8 9 A B C D E F 
Armed  Open I I I I D D I I D I I I I I T  
Armed  Short I I I I I I D D D I I I I I I   
Disarmed 
Open  T  T      T   I I T I   T  
Disarmed 
Short    T T  T       I T I    I     
24-Hour Points 
Point 
Response  0 1 2 3 4 5 6 7 8 9 A B C D E F 
Open 
I T I T      I T S T S   S  
 
 
Short 
I  I T T I T      T S    S S  
 
 
Key:  
I = Instant alarm 
 
D = Delayed alarm 
 
T = Trouble 
 
S = Supervisory 
Blank = Audible or visual response 
Example of Controlled point:  
Point Type = 1  
Point Response = 8 
Perimeter point with delayed alarm response when 
armed (opened or shorted) and no response when 
disarmed. 
Example of 24-hour point: 
Point Type = 0  
Point Response = 8 
P## Entry Delay 
Default: 
Refer to the program record sheet 
Selection:  5 sec to 600 sec 
Use this option to enter the amount of entry delay 
time that a user has after faulting a Controlled point 
(P## Type 1, 2, 3) with a delayed response (D) (P## 
Pt Response
) of 4, 5, 6, 7, or 8. DISARM NOW 
appears for the duration of the time programmed 
when the point is faulted in the delay condition. 
 
The D1255 alternates between DISARM 
NOW and the point text of the point that 
caused the area to enter into entry delay. 
If this time expires before disarming, or if the point is 
configured with an instant response (I), an alarm 
occurs. 
 
Make entries in 5 sec increments. The 
programmer does not allow off-increment 
entries. 
With Passcode Length set to a non-zero value, 
entering a valid Passcode during Entry Delay disarms 
the system as soon as the last digit is entered. No 
other keys are required. When the control panel is in 
Exit Delay or is armed, entering a valid Passcode 
must be followed by the [ENTER] or [ENT] key. 
 
If another Perimeter or Interior Follower 
Delay point trips while the area is already 
in entry delay, the control panel adjusts 
the delay time to the Delay point with the 
least amount of delay time. 
When a user enters an area, a Perimeter 
point is faulted and the entry delay starts. 
If an interior point must fault during entry 
delay to allow the user to disarm the area 
at a keypad, program P## Type as 3 
(Interior Follower). 
For SIA CP-01 Compliance: 
P## Entry Delay
 must be between 30 sec and 
240 sec.