Series Connections 
32 
Series N5700 User’s Guide  
Setting the Over-Voltage Protection 
The master unit OVP should be programmed to the desired OVP level. 
The OVP of the slave units should be programmed to a higher value 
than the master. When the master unit shuts down, it programs the 
slave unit to zero output voltage. If a slave unit shuts down when its 
OVP is set lower than the master output voltage, only that unit shuts 
down and the remaining slave units will supply all the load current. 
Setting the Over-Current Protection 
Over-current protection, if desired, may only be used with the master 
unit. When the master unit shuts down it programs the slave units to 
zero output voltage. 
Series Connections 
WARNING 
SHOCK HAZARD  For models up to 60VDC rated output, no point shall be more 
than +/-60VDC above/below chassis ground. For models > 60VDC rated 
output, no point shall be more than +/-600VDC above/below chassis ground.
There is also a potential shock hazard at the IEEE/LAN/USB ports when 
using power supplies with rated or combined voltages > 400VDC with the 
positive output of the power supplies grounded. Do not connect the positive 
output to ground when using the IEEE/LAN/USB under the above conditions.
 
CAUTION 
Only power supplies that have equivalent voltage and current ratings can be 
connected in series. 
Two units of the same voltage and current rating can be connected in 
series to provide up to two times the output voltage capability. 
Because the current is the same through each element in a series 
circuit, outputs connected in series must have equivalent current 
ratings. Otherwise, the higher rated output could potentially damage 
the lower rated output by forcing excessive current through it under 
certain load conditions. Refer to the following figures for typical 
series connections using either local or remote sensing. 
It is recommended that diodes be connected in parallel with each 
output to prevent reverse voltage during start up sequence or in case 
one unit shuts down. Each diode should be rated to at least the rated 
output voltage and output current of the power supply.