Agilent Technologies N5700 User Manual

Page of 128
Parallel Connections 
30 
Series N5700 User’s Guide  
Grounding the Output 
The output of the power supply is isolated from earth ground. Either 
positive or negative voltages can be obtained from the output by 
grounding (or "commoning") one of the output terminals. Always use 
two wires to connect the load to the output regardless of where or 
how the system is grounded.  
To avoid noise problems caused by common-mode current flowing 
from the load to ground, it is recommended to ground the output 
terminal as close as possible to the power supply chassis ground
.
 
WARNING 
SHOCK HAZARD  For models up to 60VDC rated output, no point shall be more 
than +/-60VDC above/below chassis ground. For models > 60VDC rated 
output, no point shall be more than +/-600VDC above/below chassis ground.
There is also a potential shock hazard at the IEEE/LAN/USB ports when 
using power supplies with rated or combined voltages > 400VDC with the 
positive output of the power supplies grounded. Do not connect the positive 
output to ground when using the IEEE/LAN/USB under the above conditions.
Parallel Connections 
CAUTION 
Only power supplies that have equivalent voltage and current ratings can be 
connected in parallel.  
Up to four units of the same voltage and current rating can be 
connected in parallel to provide up to four times the output current 
capability. Refer to the following figures for typical connections of 
parallel power supplies using either local or remote sensing. The 
figures show two units, however, the same connection method 
applies for up to four units.  
Local Sensing
 
+
V
-
V
+
V
-
V
+S
+LS
-S
-LS
+S
+LS
-S
-LS
MASTER
POWER SUPPLY
SLAVE
POWER SUPPLY
LOAD
J1-25
J1-10
Parallel
Current Program
As short as possible
Twisted
   pair
J1-8 J1-12