Agilent Technologies N5700 User Manual

Page of 128
Output On/Off Control 
42 
Series N5700 User’s Guide  
Output On/Off Control 
The Output On/Off control turns the power supply output on or off. 
This can be done with the front panel OUT ON button or from the 
rear panel J1 connector. With the output off, adjustments can be 
made to the power supply or the load without shutting off AC power. 
OUT ON button 
The OUT ON button can be pressed at any time to enable or disable 
the power supply output. When the output is disabled, the output 
voltage and current go to zero and the display shows OFF. 
Output Shut-Off Terminals 
Output Shut-Off (SO) terminals are available on the J1 connector to 
enable or disable the power supply output. This function is edge-
triggered. J1 pin 15 is the Shut-Off input, and pins 2 and 3, which are 
connected internally, are the signal common. All pins are optically 
isolated from the power supply output. The Shut-Off input accepts a 
2.5V-to-15V signal or an open/short contact to enable or disable the 
output. The Shut-Off control logic is selected by SW1 setup switch 5. 
When an on-to-off transition is detected at the Shut-Off input, the 
Shut-Off function enables or disables the output according to the 
signal level or the open/short applied to J1 pin 15. When the output 
has been disabled by the Shut-Off function, the display shows SO to 
indicate the output is disabled. 
To re-enable the output after it has shut down, you must disable the 
Shut-Off signal. In Auto-Restart mode, operation resumes 
automatically. In Safe-Start mode the Shut-Off function is latched. 
You must also press the OUT ON button or send an 
OUTPut:PROTection:CLEar command to resume operation. 
The Shut-Off function can be used to shut down multiple power 
supplies in a daisy-chain fashion as explained later in this chapter. It 
can also be used to reset the OVP and OCP as previously described. 
 
SW1 switch 5 
SO Signal Level 
Output 
Display 
Down (default) 
2 - 15 V or Open 
On 
Voltage/Current 
 
0 – 0.4V or Short 
Off 
SO 
Up 
2 - 15 V or Open 
Off 
SO 
 
0 – 0.4V or Short 
On 
Voltage/Current 
NOTE 
After applying AC power, the output will not be disabled by the Shut Off 
function if the Shut-Off input is in the shut-off state.  This is because the unit 
has not detected an on-to-off Shut Off transition.