D9412GV3/D7412GV3 | Operation and Installation Guide | 9.0  
Off-Board Points 
 
Bosch Security Systems, Inc. | 10/10 | F01U143070-03 
43
 
9.4.2 Listings 
The D8128D OctoPOPIT Module is UL Listed for 
Local or Police Connected Burglary Alarm, Central 
Station Burglary Alarm, Household Burglary Alarm 
applications, and commercial fire applications (UL 864 
and NFPA 72).  
The D8128D is also suitable for fire supervisory 
applications, such as indicating circuit supervision 
(using the D192G Bell Circuit Supervision Module), 
sprinkler supervision, and valve tamper protection.  
Requirements for Fire Initiation Applications 
 
Non-powered, fire initiating devices such as 
pull-stations, heat detectors, and UL Listed 
four-wire smoke detectors can be 
connected directly to the point inputs on the 
D8128D. 
 
 
For UL 864 Commercial Fire applications, 
refer to Installing Combination Fire and 
Intrusion Alarm Systems
 in the 
D9412GV3/D7412GV3 Approved 
Applications Compliance Guide
  
(P/N: F01U143069) for important 
information about combination fire and 
intrusion systems. 
The D125B Dual Powered Loop Interface Module or 
the D129 Dual Class “A” Module zone outputs can be 
connected directly to the point inputs on the D8128D. 
Use the D125B to connect two-wire smoke detectors. 
Typically, the D129 is used for connecting waterflow 
switches. 
The D125B or D129 and the OctoPOPIT can be 
mounted in the same enclosure with the control panel 
or in a separate enclosure connected to the control 
panel’s enclosure by a conduit not more than 6 m  
(20 ft.) in length. 
Figure 19:  D8128D OctoPOPIT Layout 
2 3 4 5
1
6 7 8
P O I N T S
1
2
3
4
 
1 -  Molex
®
 connectors 
2 -  Address DIP switches 
3 -  Terminal strip 
4 -  Point DIP switches