Avaya S8100 User Manual

Page of 408
1 Install and cable a G600 cabinet
Install off-premises station wiring
122
S8100 Installation and Upgrades
November 2003
Install off-premises station wiring
The local telephone company provides the cabling for off-premises stations. These stations can appear on 
any of the RJ21X network interfaces provided for the CO trunks.
!
WARNING:
Use only an FCC-approved (or equivalent) analog telephone (for example, 2500-series set) as an 
off-premises station. The TN746B and TN2183 Analog Line circuit packs can be connected to off-
premises stations.
1
Install an A25D cable between the RJ21X network interface and a sneak fuse panel.
2
At the MDF, connect jumper wires between 1 row/connecting block in the green field and up to 3 
rows/connecting blocks in the purple field to concentrate the analog line pairs.
3
Connect an A25D cable between the sneak fuse panel and the terminal block connector associated 
with the green row in Step 2.
4
Install a green label on the terminal block to identify the remote location.
5
Administer per Administrator’s Guide for Avaya Communication Manager (555-233-506).
Install off-premises or out-of-building stations
Out-of-building campus stations are telephones not physically located in the same building as the 
equipment room yet located on the same property.
Analog off-premises stations
 on page 123 shows the 
connections for 1 to 8 off-premises analog telephones. Only analog telephones connected to TN742, 
TN746B, TN2183, or TN769 Analog Line circuit packs can be installed out-of-building.
The maximum distance from the system’s cabinet to the out-of-building voice terminal is 6000 feet 
(1828.8 meters) using 24-AWG (0.26-mm
2
) wire.