 H35 Direct Vent Freestanding Gas Stove
EXTERIOR VENT TERMINAL LOCATIONS
A= 
Clearance above grade, veranda, porch, deck, or balcony *(min. 12"/30cm) 
B= 
Clearance to window or door that may be opened *(12"/30cm)
C= 
Clearance to permanently closed window *(min. 12"/30cm) 
D= 
V
e
rtical clearance to ventilated soffi
 t located above the terminal within a horizontal 
distance of (24"/60cm) from the centerline of the terminal (min. 22"/55cm) check with 
local code.
E= 
Clearance to unventilated soffi
 t (min. 12"/30cm)
F= 
Clearance to outside corner: with 
AstroCap 
T
e
rmination Cap (min. 6"/15cm), with Dura-
V
ent 
T
e
rmination Cap (min.12"/30cm), with Riser V
ent (min. 6"/15cm)
G= 
Clearance to inside corner: with 
AstroCap 
T
e
rmination Cap (min.  6"/15cm), with Dura-
V
ent 
T
e
rmination Cap (min.12"/30cm), with Riser V
ent (min. 6"/15cm)
H= 
Not to be installed above a meter/regulator assembly within (3'/90cm) horizontally from 
the centerline of the regulator
.
J= 
Clearance to service regulator vent outlet *(min. 36"/90cm)
K= 
Clearance to non-mechanical air supply inlet to building or the combustion air inlet to 
any other appliance *(12"/30cm)
L= 
Clearance to a mechanical air supply inlet *(min. 72"/1.8m)
M= 
**Clearance above paved sidewalk or a paved driveway located on public property 
*(min. 84"/2.1m)
N= 
Clearance under veranda, porch, deck, or balcony *(min. 12"/30cm)***
    
Note: * 
As specifi
 ed in CGA
 B149 Installation Code.  Note: Local codes or  regulations 
may require dif
ferent clearances.
**A
 vent shall not terminate directly above a sidewalk or paved driveway which is located 
between two single family dwellings and serves both dwellings.
***Only permitted if veranda, porch, deck, or balcony is fully open on a minimum of two 
sides beneath the fl
 oor
.
INSTALLATION