SED2 VFD Electronic Bypass Option Operating Instructions 
22 
 
Siemens Building Technologies, Inc. 
 
Parameter Description 
Action 
Setting/ 
Default 
P0003 
User Access Level 
Allows you to access more 
parameters. 
1 = Standard 
2 = Extended 
3 = Expert  
1. Press   to access parameter 
r0000 and to enter the SED2 
parameter mode. 
2. Press   to advance to 
parameter P0003
3. Press   to access the 
parameter values level. 
4. Press   to advance to 3 
(expert level). 
5. Press   to confirm and save 
the P0003 = 3 setting. 
Setting = 3 
Default = 1 
NOTE: 
Before starting quick commissioning, set P0003 = 3 to ensure all necessary parameters are available 
during quick commissioning. 
P0010 
Quick Commissioning 
0 = Ready to Run 
1 = Quick Commissioning 
30 = Factory Setting 
1. Press   to access parameter 
r0000 and to enter the SED2 
parameter mode. 
2. Repeatedly 
press   to 
advance to parameter P0010
3. Press   to access the 
parameter values level. 
4. Press   to advance to 1
5. Press   to confirm and save 
the P0010 = 1 setting. 
Setting = 1 
Default = 0 
NOTES: 
1.  P0010 must always be set back to 0 before operating the motor. 
2.  If P3900 is greater than 0 on completion of commissioning, P0010 is automatically set back to 0.