Siemens 125-3208 Manual De Usuario

Descargar
Página de 64
SED2 VFD Electronic Bypass Option Operating Instructions 
24 
 
Siemens Building Technologies, Inc. 
 
Parameter Description 
Action 
Setting/ 
Default 
P0305* 
Rated Motor Current
 
0A to 10,000A. 
Rated motor current (A) from 
motor nameplate. 
1. Press   to advance to 
parameter P0305
2. Press   to access the 
parameter values level. 
3. Press   to advance to 
nominal current. 
4. Press   to confirm and save 
the setting. 
Setting = 
Motor 
nameplate 
Default =  
Varies by 
model 
P0307* 
Rated Motor Power 
0 kW or hp to 200 kW or hp. 
Rated motor power (kW or hp) 
from motor nameplate. 
If P0100 =1 (60 Hz, hp, North 
America), then motor power is in 
hp. 
1. Press   to advance to 
parameter P0307
2. Press   to access the 
parameter values level. 
3. Press   to advance to 
nominal power. 
4. Press   to confirm and save 
the setting. 
Setting = 
Motor 
nameplate 
Default =  
Varies by 
model 
(hp/voltage 
dependent) 
P0308*, or 
P0309 
Rated Motor cosPhi (P308), or 
Rated Motor Efficiency (P0309) 
0.000 to 1.00 (P0308) or 0.0 to 
99.9 (P0309) 
Rated motor cosPhi or motor 
efficiency from motor nameplate. 
If P0100 = 2 and P0307 = kW, 
P0308 displays. 
If P0100 = 1 and P0307 = hp, 
P0309 displays. 
P0309 = 100% corresponds to 
super conducting. 
NOTE: 
This parameter is available when 
P0003 = 3 and P0010 = 1. 
1. Press   to advance to 
parameter P0308 or P0309
2 Press   to access the 
parameter values level. 
3. Press   to advance to 
nominal cosPhi or motor 
efficiency. 
4. Press   to confirm and save 
the setting. 
Setting = 
Motor 
nameplate 
P0308 Default 
= 0.00 
P0309 Default 
=  
Varies by 
model 
(hp/voltage 
dependent) 
* Motor related parameters.