Siemens 125-3208 Manual De Usuario
Startup Procedures
Siemens Building Technologies, Inc.
23
Parameter Description
Action
Setting/
Default
P0100
Operation for Europe/N.
America
America
0 = 50 Hz, kW (Europe)
factory
factory
default
1 = 60 Hz, hp
(North
(North
America)
2 = 60 Hz, kW
(North
(North
America)
The setting of Motor Frequency
and Unit of Measurement DIP
switch 2 overrides P0100
settings 0 and 1.
and Unit of Measurement DIP
switch 2 overrides P0100
settings 0 and 1.
1. Press to advance to
parameter P0100.
2 Press to access the
parameter values level.
3. Press to advance to 1.
4. Press to confirm and save
the P0100 = 1 setting.
Setting = 1
Default = 0 or
1
1
(Default is
determined by
the setting of
the motor
frequency and
unit of
measurement
DIP switches.)
determined by
the setting of
the motor
frequency and
unit of
measurement
DIP switches.)
NOTES:
1. Stop the SED2 (that is, disable all pulses) before changing this parameter.
2. Changing P0100 resets all rated motor parameters as well as other parameters that depend on the
rated motor parameters (such as P0340, Calculation of motor Parameters).
P0304*
Rated Motor Voltage
10V to 2000V.
Rated motor voltage (V) from
motor nameplate.
motor nameplate.
1. Press to advance to
parameter P0304.
2. Press to access the
parameter values level.
3. Press to advance to
nominal voltage.
4. Press to confirm and save
the setting.
Setting =
Motor
nameplate
Motor
nameplate
Default =
Varies by
model
Varies by
model
* Motor related parameters.