Startup Procedures 
Siemens Building Technologies, Inc. 
 
23 
 
Parameter Description 
Action 
Setting/ 
Default 
P0100 
Operation for Europe/N. 
America 
0 = 50 Hz, kW (Europe)  
 factory 
default 
1 = 60 Hz, hp  
 (North 
America) 
2 = 60 Hz, kW 
 (North 
America) 
The setting of Motor Frequency 
and Unit of Measurement DIP 
switch 2 overrides P0100 
settings 0 and 1.  
1. Press   to advance to 
parameter P0100.  
2 Press   to access the 
parameter values level. 
3. Press   to advance to 1
4. Press   to confirm and save 
the P0100 = 1 setting. 
Setting = 1 
Default = 0 or 
(Default is 
determined by 
the setting of 
the motor 
frequency and 
unit of 
measurement 
DIP switches.) 
NOTES: 
1.  Stop the SED2 (that is, disable all pulses) before changing this parameter. 
2.  Changing P0100 resets all rated motor parameters as well as other parameters that depend on the 
rated motor parameters (such as P0340, Calculation of motor Parameters). 
P0304* 
Rated Motor Voltage
 
10V to 2000V. 
Rated motor voltage (V) from 
motor nameplate. 
1. Press   to advance to 
parameter P0304
2. Press   to access the 
parameter values level. 
3. Press   to advance to 
nominal voltage. 
4. Press   to confirm and save 
the setting. 
Setting =  
Motor 
nameplate 
Default = 
Varies by 
model 
* Motor related parameters.