Refer to Table E-3 for the insertion losses of the fibers themselves. Use 
Table E-4, which lists the losses for connectors, cables, and splices, if the 
specifications for these components are not available.
Use Table E-3 for fiber-to-fiber connections only, not for power launched 
from a transmitter.
Example. 
Suppose that a link consisting of one km of 62.5/125 fiber with a 
maximum attenuation rating of 1.75 dB/km is transmitting into one km 
of 50/125 fiber with a maximum attenuation rating of 3 dB/km. The 
fibers are joined using a fusion splice rated at 0.3 dB and the link contains 
one in-line ST connector rated at 0.6 dB. 
Table E-3   Insertion Losses for Mating Unlike Fiber Types - Transmitting Fiber
Receiving 
Fiber Size
Numerical 
Aperture
50 µm
50 µm
62.5 µm
85 µm
100 µm
0.20
0.22
0.275
0.26
0.29
50 µm
0.20
0.0
0.4
2.2
3.8
5.7
50 µm
0.22
0.0
0.0
1.6
3.2
4.9
62.5 µm
0.275
0.0
0.0
0.0
1.0
2.3
85 µm
0.26
0.0
0.0
0.1
0.0
0.8
100 µm
0.29
0.0
0.0
0.0
0.0
0.0
Table E-4   Typical Losses for Typical Connectors, Cables, and Splices
Type of Insertion
Loss
SC connector
.6 dB
ST connector (ceramic)
.6 dB
ST connector (plastic)
1.0 dB
ST connector (stainless steel)
.7 dB
62.5/125 cable
1.0 to 3.0 dB maximum per km, depending 
on cable quality (nominal 2.0 dB)
8/125 cable
.5 dB/km (AT&T Lightguide)
Bypass switch (currently not 
available in single mode)
2.5 dB maximum
Fusion splice
1 to 3 dB depending on type used (use .3 dB)