Figure 2.8 – Airflow Through Engine/Generator
2.3.2  testIng the InstallatIon
The  manufacturer  recommends  testing  the  installa-
tion to be sure adequate cooling airflow is available to 
the unit before placing the unit into service. If the unit 
shows signs of overheating, enlarge the air openings. 
Never place a unit into service until absolutely certain 
that cooling and ventilation is adequate.
NOTE:
Test  the  installation,  especially  if  bringing  in  air 
from below the generator set.
2.4   lp gas Fuel systeM
danger
  LP gas is highly EXPLOSIVE. The gas is heavier 
than air and tends to settle in low areas. Even 
the slightest spark can ignite it and cause and 
explosion. Only competent, qualified people 
should be allowed to install, test, adjust or ser-
vice an LP gas fuel system. Install the optional 
fuel system in compliance with applicable codes, 
standards and regulations. After the installa-
tion, do not do anything that might render the 
system in noncompliance with applicable codes 
and standards.
The LP powered range of generators are fitted with a 
nonadjustable, factory set system. These systems are 
tamper-proof to meet 1997 California Air Resources 
Board requirements for engine emission.
2.4.1   parts not Included In Fuel 
systeM
The  propane  fuel  system  does  NOT  include  such 
items as (a) gas tank, (b) gas piping, (c) fittings, (d) 
valves,  and  (e)  primary  regulator,  used  to  store  the 
gaseous  fuel  and  deliver  it  to  the  gaseous  fuel  sole-
noid (Figure 2.9).
danger
  Use only approved components in the fuel sup-
ply system. All components must be properly 
installed in accordance with applicable codes. 
Improper installation or use of unauthorized 
components may result in fire or an explosion. 
Follow approved methods to test the system 
for leaks. No leakage is permitted. Do not allow 
fuel vapors to enter the vehicle interior.
Figure 2.9 – Typical Propane Gas Fuel System
2.4.2  soMe IMportant consIderatIons
When installing an LP gas system, consider seriously 
the following items:
•  All  fittings,  lines,  hoses  and  clamps  must  be 
tight  and  free  of  leaks.  Apply  a  pipe  sealant  to 
threads  when  assembling  threaded  connections. 
This reduces the possibility of leakage.
•  Test the entire fuel system for leaks using approved 
test methods.
•  Optimum gas pressure at the inlet to the gaseous 
fuel solenoid valve and secondary regulator is 11 
inches water column.
•  The  installer’s  fuel  supply  connection  point  is  at 
the gaseous fuel solenoid valve. This is a 3/4-inch 
(female)  connection.  Provide  a  suitable  3/4-inch 
NPT (male) connector to attach to the fuel supply 
line.
section 2 – Installation
recreational vehicle generator