Guardian Technologies 004701-0 Manual De Usuario

Descargar
Página de 52
 
•  Conductors must be rated 221° F (105° C) or must 
be of a larger conductor size.
2.6.3  generator ac connectIons
Generator  AC  output  leads  (BLACK)  “hot”  and 
(WHITE) grounded neutral come out of the generator 
as shown in Figure 2.13. There is also a green lead 
that  connects  to  ground  in  the  junction  box  of  the 
recreational vehicle.
Figure 2.13 – Generator AC Output Leads
342.2
[13 1/2"]
778.9
[30 11/16"]
REF.
FRONT DOOR ACCESS FOR
ALL REQUIRED MAINTENANCE
REMOTE PANEL
CONNECTOR
500.2
 [19 11/16"]
REF.
AC OUTPUT
HARNESS
HOT AIR
EXHAUST
TAIL PIPE
EXIT
OIL DRAIN
AIR
INTAKE
48.1
[1 7/8"]
222.7
[8 3/4"]
300.7
[11 13/16"]
369.7
[14 9/16"]
688.3
[27 1/8"]
29
[1 1/8"]
55.5
[2 3/16"]
376.5
[14 13/16"]
5/16"-18 WELDNUTS
(6 PLACES)
82.5
[3 1/4"]
343.4
[13 1/2"]
423.2
[16 11/16"]
717.7
[28 1/4"]
50.8
[2"]
118
[4 5/8"]
223.5
[8 13/16"]
60
[2 3/8"]
210
[8 1/4"]
176.6
[6 15/16"]
83.5
[3 5/16"]
429.5
[16 15/16"]
414.5
[16 5/16"]
360.5
[14 3/16"]
63.5
[2 1/2"]
416
[16 3/8"]
170
[6 11/16"]
79
[3 1/8"]
101
[4"]
TYP.
6.7
[1/4"]
736.4
[29"]
476.4
[18 3/4"]
36.5
[1 7/16"]
[1 7/16
[1 7/16
39.6
 [1 9/16"]
69.6
 [2 3/4"]
34.3
 [1 3/8"]
71.2
 [2 13/16"]
211.3
 [8 5/16"]
 NEG. BAT.
 CONNECTION
POS. BAT.
CONNECTION
 LP FUEL INLET
VIEW FROM TOP
NOTE: ALL AIR INTAKES AND EXHAUST OUTLETS MUST BE
      KEPT CLEAR OF ANY OBSTRUCTIONS.  ALL OPEN AREA
      IS REQUIRED FOR COOLING.
CONNECTIONS IN
BACK OF GENERATOR
Leads BLACK to WHITE are protected against over-
load  by  a  30-amp  circuit  breaker  (CB1).  Use  this 
line-to-neutral connection separately to operate 120-
volt, single-phase, 60 Hertz, AC loads requiring up to 
3,400 watts (3.4 kW) of power. 
  Do NOT connect electrical loads in excess of any 
circuit breaker rating or probems will develop 
with circuit breaker tripping, which causes a loss 
of AC output. Also, do NOT exceed the gener-
ator's rated wattage capacity. Add the watts 
or amperes of all lighting, appliance, tool and 
motor loads the generator will operate at one 
time. This total should be less than the unit's 
rated wattage/amperage capacity.
2.6.4  conduIt
Route the connections between the generator and the 
junction box through approved, flexible conduit. The 
following general rules apply:
•  Cut  wiring  to  the  required  length  and  allow  extra 
wire for junction box connections.
•  Carefully  prepare  conduit  ends  to  prevent  sharp 
edges from cutting through wiring insulation.
•  Route conduit so it does not interfere with genera-
tor movement.
•  If using metallic conduit, vapor seal the end of the 
conduit  where  it  enters  the  junction  box.  Do  this 
because flexible metallic conduit is not vaporproof 
along its entire length.
2.6.5   IsolatIng dIFFerent power 
sources
Connections from the junction box must terminate in 
a  double-pole,  double-throw  transfer  switch  (Figure 
2.14).  An  alternate  method  for  isolating  different 
power  sources  is  by  using  an  isolating  receptacle 
(Figure 2.15). Whichever method is used, be certain 
that  both  power  sources  are  NOT  connected  at  the 
same time.
2.6.6  power supply cord
The power supply cord must comply with all appli-
cable  codes,  standards  and  regulations.  It  must  be 
large enough to handle the full amperage to which it 
will be subjected.
2.6.7   ground Fault cIrcuIt 
Interrupters
The  National  Electrical  Code  (NFPA  70,  551-7) 
requires that ground fault circuit interrupters (GFCIs) 
be installed on all external and some internal electri-
cal receptacles. Contact the dealer for recommenda-
tions.
2.7   battery InstallatIon
2.7.1  recoMMended battery
Install  a  battery  that  meets  the  following  
requirements:
•  The  battery  must  be  a  12-volt,  automotive  type  
storage battery.
•  For  prevailing  ambient  temperatures  above  32° 
F  (0°  C),  use  a  battery  rated  70  amp-hours  and 
capable of delivering 400 cold-cranking amperes.
•  For  prevailing  ambient  temperatures  below  32° 
F  (0°  C),  use  a  battery  rated  95  amp-hours  and 
capable of delivering 400 cold-cranking amperes.
NOTE:
If the battery is to be used to power other vehicle 
accessories,  as  well  as  start  the  generator,  a  bat-
tery with a larger capacity may be needed.
2.7.2  battery cables
Using battery cables that are too long or too small in 
diameter may cause a drop in voltage, which causes 
starting problems. For the best cold weather starting, 
the  voltage  drop  between  battery  terminals  and  the 
generator  connection  point  should  not  exceed  0.12 
volts per 100 amperes of cranking current.
section 2 – Installation
recreational vehicle generator