Cisco ASR 9001 and Cisco ASR 9001-S Routers Hardware Installation Guide
OL-26701-02
Chapter 1      Preparing for Installation
Site Requirement Guidelines
Caution
Each Cisco ASR 9001 Router is powered by only one type of input: AC or DC. A hybrid (AC+DC) 
power configuration is not supported.
Caution
Proper grounding is necessary to avoid damage from lightning and power surges. See the 
 for grounding 
requirements.
AC Powered Routers
AC power modules operate in the input range of 100 VAC to 240 VAC, 50 to 60 Hz and require a 
minimum service of:
15 A for operation in North America and Japan
10 A for international operation
13 A for operation in the UK
Each of the AC power inputs requires a separate dedicated branch circuit. For a list of the nominal and 
acceptable value ranges for source AC power, see 
.
 lists the AC-input power cord options, specifications, and Cisco product numbers for the 
AC-input power supply modules. 
AC Power Cord Illustrations
This section contains the AC power cord illustrations, as described in 
. Note that an AC power 
cord may be used with several power supplies. 
Table 1-1
AC-Input Power Cord Options for ASR 9001 Router
Locale
Part Number
Length
Power Cord 
Rating
Reference 
Illustration
USA
CAB-AC
8.2 feet (2.5 m)
15 A, 250 V
Japan
CAB-L620P-C13-JPN
8.2 feet (2.5 m)
15 A, 250 V
Australia
CAB-ACA
8.2 feet (2.5 m)
10 A, 250 V
Italy
CAB-ACI
8.2 feet (2.5 m)
10 A, 250 V
Argentina
CAB-ACR
8.2 feet (2.5 m)
10 A, 250 V
Switzerland
CAB-ACS
8.2 feet (2.5 m)
10 A, 250 V
UK
CAB-ACU
8.2 feet (2.5 m)
13 A, 250 V
China
CAB-ACC
8.2 feet (2.5 m)
10 A, 250 V
South Africa/India
CAB-ACSA
8.2 feet (2.5 m)
10 A, 250 V
Europe
CAB-9K10A-EU
8.2 feet (2.5 m)
10 A, 250 V
Israel
SFS-250V-10A-IS
8.2 feet (2.5 m)
10 A, 250 V