Toshiba TIC-LF232A Manual De Usuario

Descargar
Página de 8
  
TIC-LF232A 
Field Intelligent Device Series 
Sanitary Electromagnetic Flowmeter 
  
Introduction 
The electromagnetic flowmeter uses Faraday’s Law of 
electromagnetic induction to measure the process flow. 
The device consists of two units: a detector, through 
which
 
the
 
fluid
 
to
 
be
 
measured
 
flows
 
and
 
in
 
which
 
low-level signals proportional to flow rates are 
obtained; and a converter, which supplies excitation 
current to the
 
detector,
 
and
 
amplifies
 
the
 
signals
 
from
 
the
 
detector and
 
then
 
processes
 
and
 
converts
 
the
 
signals
 
into
 
the
 
4–20 mA
 
dc current
 
signal.
  
The LF232 offers various outputs such as totalization 
output and multi-range selection outputs. With it 
patented Noise-Sentry original noise-suppression 
circuit and advanced algorithms. The LF232 is highly 
resistant to noise and provides a stable output even 
when measuring fluids contain slurries. The
 
LF232 can
 
be
 
used
 
with
 
a
 
separately
 
mounted
 
detector
 
such
 
as the 
LF150 or LF470. The LF232 can also be used with 
conventional models of detectors. 
The AF900 hand-held terminal (HART*
communicator) can be used to communicate with the 
flowmeter from a remote place. See the 
Communications signal specification for details about 
HART protocol. 
*1:  HART protocol (Highway Addressable Remote 
Transducer) is a communication protocol for industrial 
sensors recommended by the HCF
 
(HART
 
Communication
 
Foundation). 
 
 
Specifications 
 
Overall Specifications 
Measurement range in terms of flow velocity: 
Conbination LF150, LF470 
0 –1.0 ft/s to 0 – 32.8 ft/s (0 – 0.3 m/s to 0 –10 m/s) 
Fluid conductivity:  5µS/cm or more 
Ambient temperature: -4 to 140 °F (-20 to 60 °C) 
(Storage temperature: -13 to 149 °F (-25 to 65 °C)) 
Structure: IP67 and NEMA 4X Watertight 
 
 
 
 
 
 
 
 
 
 
 
 
 
Figure 1.  LF232 Converter 
 
Accuracy:  the accuracy is dependent on the type of 
detector combined with the LF232. See the following 
tables for accuracy when combined with specified 
detectors. 
Detector combined  
LF470 (Meter size 1/10", 1/6”, 1/4" 
(
2.5 to 6 mm)) 
Accuracy 
Flow rate as a 
percent of range
0.3–1.0m/s 1.0–10m/s 
0~50% 
±
0.8%FS 
±
0.4%FS 
50~100% 
±
0.8%FS 
±
0.8% of rate
Detector combined   
LF150 (Meter size 28” to 120” (700 to 3000 mm)) 
Accuracy: ±0.5 % of Rate* 
* This pulse output error result is established under 
standard operating conditions at Toshiba’s flow 
calibration facility, Fuchu Japan. 
* Individual meter’s measurement error may vary up 
to ± 0.8 % of Rate at 3.28 ft/s (1.0 m/s) or more and 
± 0.4% of Rate ±0.157 inch/s (4mm/s) at 3.28 ft/s 
(1.0 m/s) or less. 
* Current output: plus ± 8µA (0.05% of span). 
* Refer to individual calibration data for each 
individual meter’s measurement error. 
 
 
LF232
Field Intelligent Device Series
 
Electromagnetic Flowmeter Converter