Communications signal:
A digital communications (HART protocol) signal is
superimposed on 4 to 20 mA dc analog output
signal.
superimposed on 4 to 20 mA dc analog output
signal.
Load resistance: 240
Ω to 1 kΩ
Load capacitance: 0.25 µF or less
Load inductance: 4mH or less
Load inductance: 4mH or less
(For maximum cable length, about 2km is a
guideline length when CVV-S 1.25mm
guideline length when CVV-S 1.25mm
2
is used
under standard installation condition.)
Note: HART (Highway Addressable Remote
Trans-ducer) is a communications protocol for
industrial sensors recommended by the HCF (HART
Commu-nication Foundation).
Trans-ducer) is a communications protocol for
industrial sensors recommended by the HCF (HART
Commu-nication Foundation).
Output display:
16-character×2-line dot-matrix LCD
(With back light).
(With back light).
2 units can be selected from the flowing units: flow
velocity, instantaneous flow rate, total flow
(forward/reverse/difference flow), total count, %,
custom unit.
(forward/reverse/difference flow), total count, %,
custom unit.
Parameter settings—Parameters can be set as follows
•IR Switches: Various parameters can be set without
opening the converter housing using 4 infrared
switches (password can be set)
switches (password can be set)
•Zero adjustment: Zero point adjustment can be
started by pressing the switch in the converter.
•Digital communication: The AF 900 hand-held
terminal is needed to set parameters.
•Damping: 0.5 to 60 s (selectable in 1s increments)
“Field re-verification”
Mag-Prover
– Toshiba’s
Zero span calibration tool allows unit to be
re-calibrated and verified using internal software
program. (For more information contact Toshiba
International Corp.)
re-calibrated and verified using internal software
program. (For more information contact Toshiba
International Corp.)
Conditions when power fails:
Parameter setting values are stored in non-volatile
memory and the values will be restored when the
power returns to normal condition. The output and
display will stay as follows when power fails.
memory and the values will be restored when the
power returns to normal condition. The output and
display will stay as follows when power fails.
Current output: 0 mA
Digital output: OFF (contact open)
Digital output: OFF (contact open)
LCD display : No display
Surge protection: Surge protectors are installed in the
power supply, excitation circuit, current signal
output and digital I/O circuit.
output and digital I/O circuit.
Terminal block structure: 21-pole, screw connection
type (M4 screw)
Housing: Aluminum alloy
Coating: Acrylic resin-baked coating, pearl-gray
Coating: Acrylic resin-baked coating, pearl-gray
colored
Cable connection ports :
A cable gland is provided for each port.
OD of cable φ11 to 13 mm
Material Nylon 66
G (PF) 1/2 male screws.
Material Nylon 66
G (PF) 1/2 male screws.
Vibration resistance:
No resonance to the following levels of vibration:
• 10 to 55Hz with amplitude of 0.07mm
• Vibration of 30Hz with 29.4 m/s
• Vibration of 30Hz with 29.4 m/s
2
in 4h in each
direction will not cause any defect to unit.
Note: If the flowmeter is intended to be used in a
location where vibration is applied
constantly contact Toshiba.
Dimension and Weights:
See Figure 2