E6581341   
10 
3. Functional description 
In this section, functions added by the installation of this expansion IO card option, on 
top of the standard inverter functions, are described. 
Note: When power on or reset the inverter, the initialization of the ETB004Z terminal 
inputs and outputs are delayed about 300ms from the inverter own terminals. 
3.1. Multi-function output terminal   
Two output terminals and one relay output can be added. Function is similar to that of 
the output terminals of the inverter, so refer to the inverter instruction manual. 
 
Parameter 
Title   
Function 
Adjustment range 
Default setting 
f136
Output terminal function selection 7 (OUT5) 
0 - 255 
254 
(Always OFF)
f137
Output terminal function selection 8 (OUT6) 
0 - 255 
254 
(Always OFF)
f138
Output terminal function selection 9 (R2) 
0 - 255 
254 
(Always OFF)
 
 
Monitor 
Refer to the description on status monitor mode of inverter’s instruction manual. 
The output terminal status can be monitored by the output terminal status parameter 
(fe07), and the parameter can be monitor by the serial communication. 
 
fe07  
bit 
No. 15
14 13 12
11
10
9 8 7 6 5 4 3 2 1 0 
Symbol 
--- 
--- 
--- 
---
---
---
---
R2
OUT
OUT
R1
 
 
FL
OUT
OUT
Note: The OUT3, OUT4 and R1 are the terminal function of the expansion IO card option 1. 
OUT 
4
 
OUT 
3