E6581341   
11 
3.2. Multi-function input terminal   
Four output terminals can be added. Function is similar to that of the input terminals of 
the inverter, so refer to the inverter instruction manual. 
 
Parameter 
Title   
Function 
Adjustment range 
Default setting 
f123
Input terminal selection 13 (LI5) 
0 - 135 
f124
Input terminal selection 14 (LI6) 
0 - 135 
f125
Input terminal selection 15 (LI5) 
0 - 135 
f126
Input terminal selection 16 (LI5) 
0 - 135 
f145
 *Input terminal 13 - 20 response time selection
5 - 200ms 
* VF-PS1 does not have this parameter. 
 
Monitor 
Refer to the description on status monitor mode of inverter’s instruction manual. 
The input terminal status can be monitored by the input terminal status parameter 
(fe06), and the parameter can be monitor by the serial communication. 
 
fe06 
bit 
No. 15
14 13 12
11
10
9 8 7 6 5 4 3 2 1 0 
Symbol 
LI8
LI7 LI6 LI5
LI4
LI3
LI2
LI1
S4
S3
S2
S1 
RES 
ST
R F 
Note: The LI1 ~ LI4 are the terminal function of the expansion IO card option 1. 
 
3.3. -10V power supply 
The frequency command can be input from RX terminal with pulse and negative voltage 
using N10(-10V) and PP(+10V) power. 
 
Potentiometer 
Center position: 0V command 
Pulse side position: +10V command 
Negative side position: -10V command 
 
The recommended wiring cable length is 
less than 1.5m with shielded cable. 
 
 
 
Option Terminal
PP(+10)
RX
N10(-10V)
2kΩ
Inverter Terminal