E6581341   
12 
3.4. Multi-function analog output 
MON1, MON2 terminal output +/-10V, 0 - 10V, 0 - 20mA (4 - 20mA) analog signal. 
 
Parameter 
Title   
Function 
Adjustment range 
Default setting 
f672
MON1 terminal meter selection 
0 - 64 
(4: Output voltage) 
f673
MON1 terminal meter adjustment 
--- 
--- 
f674
MON2 terminal meter selection 
0 - 64   
(5: Compensated frequency) 
f675
MON2 terminal meter adjustment 
--- 
--- 
f688 
MON1 voltage/current output switching 
0: Voltage -10 - 10V output 
1: Voltage    0 - 10V output 
2: Current    0 - 20mA output 
f689 
MON1 output gradient characteristic 
0: Negative inclination 
(downward slope) 
Note1
 
1: Positive inclination   
(upward slope) 
f690 
MON1 bias adjustment 
-10.0 - 100.0% 
0.0 
f691 
MON1 voltage/current output switching 
0: Voltage -10 - 10V output 
1: Voltage    0 - 10V output 
2: Current    0 - 20mA output 
f692 
MON2 output gradient characteristic 
0: Negative inclination 
(downward slope) 
Note1
 
1: Positive inclination 
(upward slope) 
f693
MON2 bias adjustment 
-10.0 - 100.0% 
0.0 
Note1: When MON1 (MON2) setting is the voltage -10 - 10V output, f689 (f689) setting is invalid 
and the MON1 (MON2) gradient characteristics becomes the positive inclination. 
3.5. Differential current input (AI1+, AI1-) 
The frequency command can be input from the differential current input AI1 and AI2 
terminal current. Keep the each terminal voltage from CC terminal from -10V to 10V, and 
keep voltage under 5V between each terminal.   
Gain adjustment:
   f673 
-10V
0% 
100%
Gradient characteristics 
(f689) is invalid when the 
output setting is -10V - 10V. 
Bias adjustment:
   f690 
Example : MON1output (-10V - 10V) 
-100%
10V
 
Gain adjustment:
      f673 
0V 
0% 
100%
Gradient 
characteristics 
   f689 
Bias adjustment: 
   f690 
Example : MON1 output (0 - 10V)