Chapter 3 Creating and Editing Screens 
Note: Checking of Auto reset flags will reset the control block flags (Bits) automatically after 
the desired procedure has been executed. If this box is not checked, the system will ask the 
user to reset the flags. 
 
3.4.1 Control 
Block 
The control block is the way a PLC is used to control the HMI. Through the settings set in the 
registers, the controller which is connected to HMI can know HMI internal operation, i.e. 
screen switch, backlight on and off, current priority, curve sampling data and clear flag, etc. 
information and the user can also get the current system status of HMI. The register is a 
continuous data block and its length is from 0 to 8 words (Fig. 3-4-2). When using control 
block features, the actual length of control block is determined by the used control block 
features. For example, when Screen Switch feature (Screen Number Designation Register) is 
used, the control block must be set to a length of 1 or more. At this time, only Screen Number 
Designation Register can be used. One more example, when using History Buffer features 
(Sampling History Buffer Register), the control block must be set to a length of 4 or more. At 
this time, only Sampling History Buffer Register can be used. In addition, when using the 
function of Multi-language Setting Value Bit (System Control Flag Register), it is best that the 
length of the control block be set to 8 words. At this time, all the register in control block can 
be used. When the control block is set to a length of zero, the control block is disabled. 
The function and explanation of each WORD is listed as Table 3-4-1 below. In the following 
table, in the following example 1 we assume that the user uses a Delta PLC, so the available 
starting addresses in control block are Dn ~ Dn+7 (D0 ~ D7). In the following example 2, we 
assume that the user uses HMI internal register $, so the available starting address in control 
block is$n ~ $n+7 ($15 ~ $22). The user can choose if the control block designations are 
stored in PLC or HMI. 
Example 1 
(PLC register) 
Example 2 
(HMI register) 
Word 
Number 
Register Number 
Address  Example  Address  Example 
Screen Number Designation Register (SNIR)  Dn 
D0 
$n 
$15 
Control Flag Register (CFR) 
Dn+1 
D1  
 
$n+1 
$16 
Curve Control Register (CUCR) 
Dn+2 
D2 
$n+2 
$17 
Sampling History Buffer Register (HBSR) 
Dn+3 
D3 
$n+3 
$18 
Clearing History Buffer Register (HBCR) 
Dn+4 
D4 
$n+4 
$19 
Recipe Control Register (RECR) 
Dn+5 
D5 
$n+5 
$20 
Recipe Number Designation Register (RBIR) 
Dn+6 
D6 
$n+6 
$21 
System Control Flag Register 
Dn+7 
D7 
$n+7 
$22 
Table 3-4-1 Control Block Designations 
 
Revision May, 2010 
 
 
3-25