Chapter 3 Creating and Editing Screens 
   
 
Fig. 3-4-3 Communication tab            Fig. 3-4-4 PLC Connections 
Communication retry times 
is 3 times 
 
Enable / Disable Backlight 
Bit 1 controls the backlight of HMI. When bit 1 is turned ON, the HMI backlight turns 
OFF. When bit 1 is turned OFF, the HMI backlight turns ON. For example (refer to Table 
3-4-1), if D1 is set to 2 or $16.1 is set to 1, this flag is enabled and the HMI backlight 
turns OFF. When D1 = 2, it indicates that Bit 1 of D1 is 1(0000 0000 0000 0010). 
 
Enable / Disable Buzzer 
Bit 2 controls the buzzer of HMI. When bit 2 is turned ON, the HMI buzzer turns OFF. 
When bit 2 is turned OFF, the HMI buzzer turns ON. For example (refer to Table 3-4-1), 
if D1 is set to 4 or $16.2 is set to 1, the HMI buzzer turns ON. At this time, if an alarm 
occurs, it will sound. When D1 = 4, it indicates that Bit 2 of D1 is 1 (0000 0000 0000 
0100). 
 
Clear Alarm Buffer 
Bit 3 clears the alarm buffer. When an alarm history table is used, setting this bit is 
able to clear all data inside of that table. When bit 3 is turned ON, the alarm buffer is 
cleared. To clear the alarm buffer again, this flag must be turned OFF and then ON 
again. For example (refer to Table 3-4-1), if D1 is set to 8 or $16.3 is set to 1, this flag 
is turned ON and the alarm buffer will be cleared. When D1 = 8, it indicates that Bit 3 
of D1 is 1 (0000 0000 0000 1000). 
 
Clear Alarm Counter 
Bit 4 clears the alarm counter. When an alarm frequency table is used, setting this bit 
is able to clear the values for the alarms. When bit 4 is turned ON, the alarm counter is 
cleared. To clear the alarm counter again, this flag must be turned OFF and then ON 
again. For example (refer to Table 3-4-1), if D1 is set to 16 or $16.4 is set to 1, this flag 
is turned ON and the alarm counter will be cleared. When D1 = 16, it indicates that Bit 
4 of D1 is 1 (0000 0000 0001 0000). 
 
Revision May, 2010 
 
 