Chapter 3 Creating and Editing Screens 
 
Screen Number Designation Register (SNIR) 
To use this register, write a value of the screen number that the user desires to have 
displayed into this register; then HMI will change to that screen. For example (refer to 
Table 3-4-1), if set D0 or $15.0 to 1, HMI will change to the 1st screen. If set D0 or $15.0 to 
7, HMI will change to 7th screen. 
Control Flag Register (CFR) 
Bit 
Binary Display of Relative 
Position (x) 
Function 
0000 0000 0000 000x 
Enable / Disable Communication 
0000 0000 0000 00x0 
Enable / Disable Backlight 
0000 0000 0000 0x00 
Enable / Disable Buzzer 
0000 0000 0000 x000 
Clear Alarm Buffer 
0000 0000 000x 0000 
Clear Alarm Counter 
0000 0000 00x0 0000 
Update USB Data 
6-7 
0000 0000 xx00 0000 
Reserved 
0000 000x 0000 0000 
Set User Security Level (Level 1) 
0000 00x0 0000 0000 
Set User Security Level (Level 2) 
10 
0000 0x00 0000 0000 
Set User Security Level (Level 4) 
11-15 
xxxx x000 0000 0000 
Reserved 
 
Enable / Disable Communication 
Bit 0 controls the HMI communication. When bit 0 is turned ON, HMI communication is 
disabled. When bit 0 is turned OFF, HMI communication is enabled. By checking 
Communication Interrupt check box (Fig. 3-4-3) under the Communication tab of 
the Configuration dialog box when communication between one certain PLC is lost 
this bit will be turned ON and disable the communication automatically and the 
communication fault message will not display (this will not affect the communications 
between other PLCs). Then, the user can clear it to enable the communication again. If 
this check box is not checked, this flag is disabled (To disable and enable the 
communication manually, the user can use OPENCOM/CLOSECOM macro commands. 
For more details on macro commands, please refer to section 3.14) 
For example (refer to Table 3-4-1 and Fig. 3-4-4), if the PLC which is connected via 
COM2 port has communication error and communication retry time has reached three 
times, HMI will disable the communication between that PCL automatically (but will 
not disable the communication between other PLCs) and will not show communication 
errors. At this time, if D1 or $16.0 is set to 0, i.e. the communication flag is turned 
OFF, the communication will be enabled again and HMI will communicate with that 
PLC again. If the communication is lost for three times, this flag will be ON again. 
When D1=0, it indicates that Bit 0 of D1 is 0 (0000 0000 0000 0000). 
3-26 