Chapter 3 Creating and Editing Screens 
 
3-38 
Revision May, 2010
 
 
Flag Control 
Level 
ON 
 
Binary Display 
Level 6 
Bit 9, Bit 10 
Bit 8 
0000 0110 0000 0000 
Level 7 
Bit 8, Bit 9, Bit 10 
 
0000 0111 0000 0000 
Screen Number Status Register (SNSR) 
This register stores the last screen number (includes sub screen) that the user opened 
(refer to D11 or $26 of Table 3-4-2).   
Curve Control Status Register (CCSR) 
Bit 
Binary Display of Relative 
Position (x) 
Function 
0000 0000 0000 000x 
Curve Sampling Status Flag 1 
0000 0000 0000 00x0 
Curve Sampling Status Flag 2 
0000 0000 0000 0x00 
Curve Sampling Status Flag 3 
0000 0000 0000 x000 
Curve Sampling Status Flag 4 
4-7 
0000 0000 xxxx 0000 
Reserved 
0000 000x 0000 0000 
Curve Clear Status Flag 1 
0000 00x0 0000 0000 
Curve Clear Status Flag 2 
10 
0000 0x00 0000 0000 
Curve Clear Status Flag 3 
11 
0000 x000 0000 0000 
Curve Clear Status Flag 4 
12-15 
xxxx 0000 0000 0000 
Reserved 
 
Curve Sampling Status Flag 
When the HMI samples a trend graph or X-Y chart, the curve sampling status flag (bits 
0 to 3) is turned ON. After the sampling operation is completed, the curve sampling 
status flag is turned OFF. Curve Sampling Flag 1 of control block corresponds to Curve 
Sampling Status Flag 1 of status block, Curve Sampling Flag 2 of control block 
corresponds to Curve Sampling Status Flag 2 of status block and vise versa.   
 
Curve Clear Status Flag 
When the HMI clears trend graph or X-Y chart, the curve clear status flag (bits 8 to 11) 
is turned ON. After the clear operation is completed, the curve clear status flag is 
turned OFF. Curve Clear Flag 1 of control block corresponds to Curve Clear Status Flag 
1 of status block, Curve Clear Flag 2 of control block corresponds to Curve Clear 
Status Flag 2 of status block and vise versa.