Configuration saving and switching
60
Restore configuration
The restore configuration command is executed using bit 2 of the extended control word
(CMI)
.
The return to factory settings command is executed using bit 0 of the extended control word
(CMI)
. The type of setting is determined by the
active macro configuration parameter
[Macro configuration]
(CFG)
and by the
[PARAMETER GROUP LIST]
(FrY)
parameter which
defines the parameter groups concerned.
The restore command is only active if the drive is stopped, and not in "5-Operation enabled" state.
Display
terminal
Configuration 0
(EEPROM)
Configuration 1
(EEPROM)
Configuration 2
(EEPROM)
Factory settings
Industrial
HMI
terminal
PLC
Modbus
CANopen
Network
Current
configuration
(RAM)
Extended control word:
Restore configuration (CMI,2)
Set to 1
Display
terminal
Configuration 0
(EEPROM)
Configuration 1
(EEPROM)
Configuration 2
(EEPROM)
Factory settings
Industrial
HMI
terminal
PLC
Modbus
CANopen
Network
Current
configuration
(RAM)
Extended control word:
Factory setting (CMI,0)
Factory setting (CMI,0)
Set to 1
[Macro configuration]
(CFG)