Configuration saving and switching
 
60
Restore configuration
The restore configuration command is executed using bit 2 of the extended control word 
(CMI)
.
The return to factory settings command is executed using bit 0 of the extended control word 
(CMI)
. The type of setting is determined by the 
active macro configuration parameter 
[Macro configuration]
 
(CFG)
 and by the 
[PARAMETER GROUP LIST]
 
(FrY)
 parameter which 
defines the parameter groups concerned.
The restore command is only active if the drive is stopped, and not in "5-Operation enabled" state.
Display 
terminal
Configuration 0
(EEPROM)
Configuration 1
(EEPROM)
Configuration 2
(EEPROM)
Factory settings
Industrial
HMI
terminal
PLC
Modbus
CANopen
Network
Current 
configuration
(RAM)
Extended control word:
Restore configuration (CMI,2)
Set to 1
Display 
terminal
Configuration 0
(EEPROM)
Configuration 1
(EEPROM)
Configuration 2
(EEPROM)
Factory settings
Industrial
HMI
terminal
PLC
Modbus
CANopen
Network
Current 
configuration
(RAM)
Extended control word:
Factory setting (CMI,0)
Set to 1
[Macro configuration]
(CFG)