Configuration saving and switching
 
62
When the configuration or motor switching function is configured on inputs or on control word bits, to save a configuration that is already 
active, set bit 1 of the extended control word 
(CMI)
 to 1.
When the configuration or motor switching function is configured on inputs or on control word bits, bit 2 of the extended control word 
(CMI)
must be set to 1.
The configuration switching commands are only active if the drive is stopped, and not in "5-Operation enabled" state.
Display 
terminal
Configuration 0
(EEPROM)
Configuration 1
(EEPROM)
Configuration 2
(EEPROM)
Factory settings
Current 
configuration
(RAM)
Extended control word:
Save configuration (CMI,1)
Active
configuration
(CNFS)
Industrial
HMI
terminal
PLC
Modbus
CANopen
Network
Set to 1
1
2
3
Display 
terminal
Configuration 0
(EEPROM)
Configuration 1
(EEPROM)
Configuration 2
(EEPROM)
Factory settings
Current 
configuration
(RAM)
Extended control word:
Restore configuration (CMI,2)
Active
configuration
(CNFS)
Industrial
HMI
terminal
PLC
Modbus
CANopen
Network
Set to 1
1
2
3